About this document
Purpose
The HUB portal is a web application that connects directly with your Embion EMS controller, giving you centralised control over your energy plant. From here, you can configure settings and monitor performance in real time.
This guide walks you through the HUB portals key features and functions. By the end, youll understand how to optimise your renewable energy resources effectively.
Intended Audience
This document is for installation technicians and end-users who need to monitor and manage their energy systems using the HUB portal.
Callout conventions
This document uses the following admonition types as callouts:
Used for general notes in this documentation |
Used for expressing warnings in this documentation |
Used for important notes in this documentation |
Used for general tips in this documentation |
Used for caution notes in this documentation |
About the HUB Portal
Introduction
The HUB Portal is used to monitor, configure, and control your Embion EMS controllers. Each Embion EMS controller can be connected to a single EMS Site (Namespace), where an EMS Site can hold multiple Embion EMS controllers. The EMS Site can be shared with multiple users, where each user has their own privileges.
Each Embion EMS controller requires a licence once the trial period ends. The licence type is determined by the devices features, transport power capacity, and any add-ons.
Maintenance

Embion conducts periodic maintenance on the HUB Portal to implement updates, security enhancements, and performance improvements.
During scheduled maintenance, the portal may experience slower performance or temporary downtime while certain features are optimised. A maintenance banner will be displayed several days in advance to notify users.
We appreciate your patience during these necessary maintenance windows.
Mobile app installation
By following the instructions below, users can enjoy a cleaner, more immersive view of the HUB Portal on mobile devices.
iOS (Safari)
To install the HUB web application, users should follow these steps:
- Browse to https://hub.embion.nl
- Click on the “Share” button
- Click on “Add to home screen”
- Click on “Add”
![]() | ![]() | ![]() |
Android (Google Chrome)
To install the HUB web application, users should follow these steps:
- Browse to https://hub.embion.nl
- Click on the “Options” button
- Click on “Install application”
- Click on “Add”
![]() | ![]() | ![]() |
HUB Portal user account
Each user of the HUB Portal should have their own account. Account settings include country and language preferences. Users can create a new EMS Site or join an existing one.
Create account
Visit https://hub.embion.nl and click "Dont have an account?" to begin registration.
![]() | ![]() |
Registration Process
A registration form will open where you can enter your information. The registration form is in two parts:
- Company: These details will be tied to an Enterprise account, this is the account for the company and can have multiple users attached.
- Administrator account: These details are for your personal user account. Additionally, your account will have the administrator role for the Enterprise account. Each Enterprise has at least one administrator.
If your company already has a registered Enterprise, please contact an administrator to invite you. If your plant is managed by another company, ask them to invite you to the appropriate EMS Site so you can view your plant details. |
After creating your account, you can enable two-factor authentication if needed. Before proceeding, please read and agree to the terms and conditions and privacy policy. Once all fields are completed, the "Create company account" button becomes active. An activation email will be sent to your email address—click the "Activate account" link to complete setup and log in.
Account recovery
When a user has forgotten their password, they can recover it by pressing the “Reset password” button. This will open a pop-up requesting the user’s email address. Please provide the email address associated with the HUB.
If the entered email address is recognised, an email containing a reset password link will be sent to the provided email address. By clicking on the link, the user can enter a new password.
If you do not have access to the email address associated with your account, please contact your sales representative for assistance.
![]() |
Account settings
Once a user has created and logged into a HUB account, they can change their account settings by pressing the profile image in the top right corner of the HUB Portal and navigating to ‘My Account’. These settings include personal information, notifications, and security settings.
![]() |
Account Details
In the Personal Information and Language sections of the account settings, users can update the following details:
- First and Last Name
- Country
- Language - This language will be displayed on the HUB portal.
Notifications
In the Notification Settings section of account settings, users can control whether or not receive notifications. If users choose to enable notifications, they can fine-tune their preferences for different types of notifications. Additionally, when enabling sounds on the HUB, notifications and alert will play a sound on receive.
Users can define settings for the following five notification types:
- Announcement
- Success
- Warning
- Error
- Verified
For each type, users can choose to receive notifications through the portal and/or via email. This allows users to customise how they stay informed based on their preferences.
![]() |
Notifications can be accessed by pressing the bell icon in the top right corner of the HUB Portal.
When a notification is received, the bell icon will display the number of unread notifications. Each notification will show an icon indicating the type of notification.
![]() |
The notification types are defined as:
Announcement
- Invite to EMS Site
- An user joined EMS Site
- An user left EMS Site
- An user creates a join request for EMS Site
- General HUB Portal announcements
Success
- You joined EMS Site successfully
- You left EMS Site successfully
- You successfully created a join request for an EMS Site
- Device went (back) online
Warning
- Pricing scheme expires soon (1 week and 1 day before expiring)
- Pricing scheme expired
Error
- Device went offline
Verified
- EMS Site successfully promoted to enterprise
- EMS Site successfully linked to enterprise
2FA Security
Two-factor authentication adds an extra layer of security to users accounts by requiring not only their password but also a second form of verification. To set up 2FA for their HUB Portal account, users should follow these steps:
-
Download Authenticator App: Users need to download either the Microsoft Authenticator app or the Google Authenticator app on their mobile device. These apps generate unique verification codes that users will use along with their password when logging in.
-
Scan QR Code: Once users have installed the authenticator app, they should navigate to the Security section of their HUB account settings. Here, they will find a QR code displayed. Users should use the authenticator app to scan this QR code.
-
Verify Code: After scanning the QR code, the authenticator app will generate a unique verification code. Users should enter this code into the appropriate field within the HUB Portal to complete the setup process.
Once two-factor authentication is enabled, users will be prompted to enter a verification code from their authenticator app each time they log in, providing an additional layer of security to their HUB account.
EMS Sites
An EMS Site (Namespace) is basically a group of one or more Embion EMS Controllers intended for the same location or area. Connected users have access and each user has their own permissions based on their role inside the EMS Site. Device data can be monitored on dashboards which can be created or read by users with the correct permissions. EMS Sites are always linked to an Enterprise.
When a user who does not have access to any EMS Site logs in, they will need to create a new one. An EMS Site can be created by navigating EMS Sites from the Enterprise section in the left-hand sidebar and then clicking "Create" in the top-right corner.
![]() |
Create an EMS Site
When a user without access to any EMS Site (Namespace) is logged in, it will be prompted to create a new EMS Site. Also, an EMS Site can be created by navigating to the EMS Sites tab under Enterprise and clicking create in the upper right corner.
![]() |
During the process of creating an EMS Site, you have the freedom to choose a name for the EMS Site. It is advised to select a distinguishable name that helps to differentiate it from other EMS Site. You are free to use any name of your choice.
Additionally, you have the option to select a symbol to enhance the visibility and divisibility of the EMS Site.
When the EMS Site is created it will be part of the current Enterprise. The Primary Contact will receive an invite to join the EMS Site (as an admin). Further users can be invited from the EMS Site detail page.
Change EMS Site
When a user wants to switch between EMS Sites (Namespaces) they are already a member of, the following steps should be taken:
Locate the EMS Site selection button situated in the top left corner of the interface. Press the EMS Site selection button to initiate a pop-up window. Within the pop-up window, all the EMS Sites accessible to you will be displayed. Identify the desired EMS Site from the list and click on it. By selecting the EMS Site, you will be instantly switched to the chosen EMS Site, and the interface will be updated accordingly. By following these steps, users can seamlessly switch between the EMS Sites they are already members of, granting them access to the specific content and features associated with each respective EMS Site.
![]() |
EMS Site settings
EMS Site (Namespace) settings can be reached by navigating to EMS Sites within the Enterprise tab and clicking on the EMS Site you want to look into. This opens up the EMS Site details page with address and contact details, as well as a list of connected devices, users and roles.
- Users: Users can invite or approve other users to their EMS Site and assign roles to them.
- Roles: User roles can be managed here. Different roles can be made with their own permissions.
- Devices: All devices that are connected to the EMS Site are listed in a table view for easier access.
![]() |
EMS Site users
Navigate to the "Users" tab under Overviews in the EMS Site (Namespace) details page to show all active and pending users within the EMS Site. By pressing on the username, the user roles can be applied. There are also checkboxes to determine if the user is an admin and whether the user should receive notifications for this specific EMS Site.
![]() |
Invite user
New users can be invited by pressing "Invite" in the top right corner of the overview tab on the EMS Site (Namespace) details page. A pop-up will appear asking for the user’s email address. It’s also possible to use the checkbox to make the invited user an admin straight away.
![]() |
EMS Site roles
In each EMS Site (Namespace), custom roles can be assigned to users. By default, certain roles are available, but they can be modified as per the requirements. If needed, new custom roles can be created.
![]() |
Make new roles
New custom roles can be created by following these steps:
- Click on the “Create role” button located in the top right corner of the interface.
- This action will initiate the role creation process.
- Provide a name and define the specific permissions and access levels associated with the new role.
- Save the created role to add it to the list of available roles within the EMS Site (Namespace).
By utilising the “Create role” functionality, you can tailor the roles within the EMS Site to suit your specific needs. This allows for fine-grained control over user permissions and ensures that each user has the appropriate access and privileges based on their assigned role.
![]() |
Settings
EMS Site (Namespace) settings like name and image can be set here. By pressing the image a new avatar for the EMS Site can be uploaded, the recommended size of the avatar is 150x150 pixels.
![]() |
Remove EMS Site
An EMS Site (Namespace) can be removed only by administrators within the EMS Site. It can be done by clicking the “Remove EMS Site” button in the right corner of the EMS Site settings.
All devices should be removed from the EMS Site before it’s possible to remove the EMS Site. |
Enterprise
Enterprise options can be found within the EMS Site (Namespace) settings.
![]() |
Within the Enterprise options, a join request to an Enterprise can be made. Once accepted by the Enterprise, the Enterprise gains access to manage settings, devices and users (all with administrator privileges).
Once the EMS Site has been accepted by the Enterprise, it will be displayed in the header and EMS Site users overview of the EMS Site which it is managed by the Enterprise. Users within this EMS Site have the ability to switch between themes specially created by their managing Enterprise. The image below displays an EMS Site managed by an Enterprise.
![]() |
Join request
An administrator within the EMS Site (Namespace) has the ability to initiate a join request for an Enterprise by inputting the Enterprise token provided by the Enterprise.
![]() |
Enterprises
The Enterprise feature allows users to upgrade a standard EMS Site to an Enterprise variant, offering advanced functionality to manage multiple EMS Sites within this Enterprise. By inviting EMS Sites to join, Enterprises enable them to gain access to manage the EMS Site at an Enterprise level, eliminating the need for end-users to set up their EMS Site and providing both a simpler user experience and improved Enterprise management capabilities.
![]() |
Enterprises have the feature to create custom themes, enhancing the visual experience for users across EMS Sites within the Enterprise. These themes can be crafted using company colours and logo’s, ensuring a consistent organisational look across all EMS Sites linked to the Enterprise.
Enterprise features
EMS Sites
![]() |
On the EMS Sites (Namespaces) page, it is possible to manage all connected EMS Sites. It possible to create new EMS Sites which are directly linked to the Enterprise, allowing to set them up before inviting end-users.
Invite EMS Sites
For Enterprise users, adding existing EMS Sites (Namespaces) to the Enterprise isn’t directly possible. Instead, a user within the EMS Site must create a join request. To do this, they need a token, which can be found by pressing the invite button on the EMS Site overview or within the Enterprise details in the settings section.
![]() |
When an EMS Site creates a join request, Enterprise users will receive a notification within the HUB. Upon acceptance or rejection, EMS Site users will receive a notification informing them of the status of their request. |
Switch EMS Sites
When a user is a member of an Enterprise, Enterprises will appear within the EMS Site (Namespace) selector. This allows Enterprise users to easily switch between EMS Sites they have access to, without needing to open the Enterprise section.
![]() |
When Enterprise users visit an EMS Site connected to the Enterprise, their role within the Enterprise determines their role within the connected EMS Site. |
Devices
On the devices page, users can view all connected devices within EMS Sites (Namespaces) linked to the Enterprise. Various information about the devices will be displayed here.
![]() |
The following details can be read from the devices:
- Online / offline status
- Name of the device
- EMS Site in which the device is registered
- Run status, error and warning amount
- Plant control status
- Status message
- Device software status
- Product and serial number
- Dates of last data and status calls
Join requests
When an EMS Site (Namespace) wants to join the Enterprise and has created a join request, those requests are listed here, giving the Enterprise the ability to accept or reject them.
![]() |
When an EMS Site creates a join request, Enterprise users will receive a notification within the HUB. Upon acceptance or rejection, EMS Site users will receive a notification informing them of the status of their request. |
Notifications
As an Enterprise, it is possible to receive notifications from managed EMS Sites (Namespaces). This means when, for example, a device goes offline or a pricing scheme expires in an EMS Site managed by the Enterprise, the Enterprise users can receive these notifications based on their personal and Enterprise notification settings. Additionally, an entire EMS Site within the Enterprise can be completely muted if preferred, which can be done within the EMS Sites overview.
Notification preferences for each user can be changed by selecting the user and adjusting the settings.
![]() |
EMS Sites within the Enterprise can be completely muted if preferred, which can be done within the EMS Sites overview. |
Settings
Enterprises can manage notification settings for each user. Administrators can customise which types of notifications users receive and decide which notifications will (also) send an email.
![]() |
These settings do not override personal account settings. For example, if a user disables warnings in their personal account settings, they will not receive any warnings notifications, even if the Enterprise settings enable them. |
Custom notification
Enterprises have the ability to send custom notifications to all or selected EMS Sites (Namespaces) they manage. They can choose the type of notification and decide whether it will be sent to all users or only to EMS Site administrators.
![]() |
Text within custom notifications can be styled within the input field and links can be created. |
Themes
Enterprises have the feature to create custom themes, enhancing the visual experience for users across EMS Sites (Namespaces) within the Enterprise. These themes can be crafted using company colours and logo’s, ensuring a consistent organisational look across all EMS Sites linked to the Enterprise.
When a new EMS Site is created or linked to the Enterprise, the default theme is automatically set for the users within the EMS Site.
![]() |
Multiple themes can be created, allowing users within connected EMS Sites to choose one based on their preferences. |
![]() |
Portal style
When creating a theme, several colours can be changed to change the overall look across the HUB platform. For now these colours and settings can be defined within the portal section of the theme.
- Primary colour - Used in the header, badges, and titles throughout the portal
- Secondary colour - Used as background on pages and element throughout the portal
- Accent colour - Used as background within several elements throughout the portal
- Shadow colour - Used as shadow on several element throughout the portal
- Border radius - Change the border radius of element throughout the portal
When defining a theme, HEX, RGB, and RGBA colours are supported. |
Graph colours
![]() |
Custom graph colours can also be defined when creating a theme.
Basic data
Colours for the following data within basic widgets on dashboards can be set:
- Solar power
- Grid power
- Plant power
- Plant power direct solar
- Plant power direct grid
- Relative plant solar
- Relative plant grid
- Battery power
- EV charger power
- Actual reduction
EPEX data
Colours for the data within EPEX widgets on dashboards can be set. There are four sets, where positive 1 corresponds to negative 1, and so forth.
- EPEX positive (1-4)
- EPEX negative (1-4)
Advanced data
Colours for data within Advanced widgets on dashboard can be set. There is a total of ten colours that can be defined. Advanced widgets will use these colours based on how many graphs get drawn. For example: An advanced widget with four data sets will use the first four colours defined here.
Example
Example of a dashboard with the use of custom colours defined in a theme.
![]() |
Dashboard templates
Enterprises can create dashboard templates, making it easier to configure dashboards across all linked EMS Sites (Namespaces).
When a new EMS Site is created or linked to the Enterprise, users within the EMS Site can select one of these pre-configured dashboard templates when creating a new dashboard.
This feature reduces the time and effort required to set up new dashboards.
![]() |
Within the Enterprise section, a template plug-in is available where Enterprise users can manage their templates. The following options are available in this overview:
- View templates - This will open the dashboard section where the templates can be made
- Enable or disable templates - This will enable or disable the ability for linked EMS Sites to select the template
- Delete templates - This will remove the dashboard template (and dashboard itself within the dashboard section)
Create dashboard template
Templates can be created by opening the ‘Dashboard templates’ section from within the Enterprise. When creating a new dashboard, there is an option to enable the dashboard as a template (check the box for Enable template).
All available widgets can be used to create the template. The configuration settings of the widgets will also be saved within the template, allowing Enterprise users to pre-define widget configurations based on the template.
![]() |
Enterprise users can create new dashboard templates and enable them later. This allows them to set up and configure the dashboard before making it available to users in the linked EMS Sites. |
Widget features
Enterprises can use additional configuration settings in widgets when creating dashboard templates. Currently, only the Plant Overview widget includes these additional settings, but more widgets will support them in future updates.
Plant overview
EMS Site image instead of icon
In addition to the default icons, Enterprise users can enable an option to display the uploaded EMS Site (Namespace) image as an icon in the Plant Overview widget.
Select dashboard template
![]() |
Dashboard templates can be selected and used across all linked EMS Sites (Namespaces). When a user in a linked EMS Site opens the dashboard section and no dashboards have been created yet, a message is displayed in the centre of the screen.
![]() |
To create a dashboard, click the Create button in the top right. You can then give the new dashboard a name, colour and icon, and select a template to base it on. If no template is selected, an empty dashboard is created.
When a dashboard template is selected, all widget configuration settings are copied from the template. If an EMS Site has only one connected device, that device is automatically selected in the configuration of widgets that require a device. Otherwise, you must open the configuration settings and select one of the connected devices.
If an EMS Site has only one connected device, that device is automatically selected in the configuration of widgets that require a device. Otherwise, you must open the configuration settings and select one of the connected devices the first time you use the widget. |
Enterprise user management
Users
![]() |
The users page shows all active and pending users within the Enterprise, new or existing users of the HUB can be added by pressing the invite button. By pressing the user, roles can be applied.
When Enterprise users visit a connected EMS Site (Namespace), their role within the Enterprise determines their role within the EMS Site.
By pressing the settings icon the user can be made admin or can be removed.
Roles
![]() |
In each Enterprise, custom roles can be assigned to users. By default, certain roles are available, but they can be modified as per the requirements. If needed, new custom roles can be created.
When Enterprise users visit a connected EMS Site, their role within the Enterprise determines their role within the EMS Site. |
Connected Enterprise
![]() |
When an EMS Site (Namespace) is connected to an enterprise, the Enterprise will be displayed in the user overview within that EMS Site.
Devices
The devices section can be accessed by selecting the devices icon located in the left side menu or by clicking the button on the homepage.
![]() |
On this page, users can register devices within their EMS Site (Namespace). The devices section offers several features that allow users to remotely access their devices:
Device Status: This feature displays the current status of devices within the EMS Site, providing users with real-time information.
Access Token: Users can obtain an access token to make requests and retrieve data from the API, ensuring secure and authenticated access.
Device Settings: This functionality allows users to remotely modify settings on their devices and apply the changes accordingly.
Support Mode: By enabling support mode, users can grant access to manufacturer support employees. This enables the support team to reach and assist with the device as needed.
These features provide users with convenient and efficient ways to manage and interact with their devices from a remote location.
Register new device
![]() |
When registering a new device, users are required to input the serial number and pin code of the device to be registered. Both of these can be found on the label located at the right side of the device or you can find them in the menu using the front display on the device. Users should refer to the label or device menu in order to retrieve the necessary information for a successful registration.
![]() |
Device status
The device status feature allows users to quickly view an overview of all their devices and their respective statuses. A device can have one of the following statuses:
Online: The device is powered on and reachable over the internet.
Offline: The device is powered off and/or not reachable over the internet.
Support Mode: The device is online, reachable over the internet, and support mode is enabled by the user. This allows the manufacturer support team to remotely access the device to provide support.
![]() | ![]() | ![]() |
Device overview
To get more information about a device, it is possible to open a device overview form by selecting the device. It will show more detailed information about:
- Device status
- Last configuration
- Plant control
- Device information
- Contact information
- Licences
![]() |
Device options
There are several device options accessible by opening the option menu by pressing the three dots located at the upper right corner of a listed device.
![]() |
The following options are available:
Device settings Users can modify device settings and apply them remotely. This allows for convenient management of the device’s configuration.
Access tokens Users have the ability to obtain an access token. This token enables them to make requests and retrieve data from the public API securely and with authentication.
Third party access (Embion EMS only) Users can manage third-party access to their devices. These third parties can use the public API to monitor and/or control the device if access is granted.
Enable support / Disable support Users can enable support mode for their devices (or disable it when the support mode is currently enabled).
Asset Status Check (Embion EMS only) Users can manually test whether plant control commands can successfully control the assets (battery, PV, and EV charger) within their installation.
Incidents & Event Log (Embion EMS only) The Incidents & Event Log feature provides monitoring and diagnostics for connected devices and their assets.
Remove This option removes the device from the list of devices within the current EMS Site (Namespace). It is important to note that deleted devices can be added again at a later time if needed (serial number and pin code are required).
These options provide users with flexibility and control over the management of their devices registered within the EMS Site.
Licences
Device licence
Licence information is displayed within the device information, along with its expiration date. The status LEDs indicate the status of a licence feature or add-on. Possible statuses are:
Activated (green): The licence is active on the device.
Expired (red): The licence is expired.
Not activated (grey): The licence is assigned to the device, but not activated yet.
![]() | ![]() |
Add licence
To add a licence to a device, users needs to fill in the following details:
- Licence code
- CCV code
![]() |
Access tokens
Multiple access tokens can be created for each device, granting access to the public API. These tokens enable interaction with the public API and remotely read or control the plant connected to the device. By default, a total of 10.000 API calls per day are permitted for each device, and these calls can be distributed among the multiple tokens associated with the device.
When generating an access token, users have the option to specify a maximum number of requests allowed for that particular token. This feature allows you to set a limit on the number of API requests that can be made using the token. If you prefer the token to have no request limit (always limited to the maximum of 10.000 calls per device), you can leave the maximum requests value as 0.
Managing access tokens and their corresponding request limits gives you the flexibility to control API usage and optimise resource allocation for each device effectively.
![]() |
The list of tokens shows all the currently available access tokens, and allows the user to create a new one by pressing the “Generate token” button. Per token the expiration date can be selected, and the uid’s (meters and inverter) to which the token has read access can be selected.
Additional licences are available to increase the maximum number of API requests per day per device beyond the default limit. For more information about licensing options and pricing, please contact sales. They will assist you in selecting the suitable licence to meet your specific needs. |
Add tokens
To add a new access token, users are required to provide the following inputs:
Token name: Users should enter a descriptive name for the access token to easily identify its purpose or the associated device.
Expire date: (Optional): Users can specify the expiration date for the access token. Once the expiration date is reached, the token will no longer be valid.
Enable control access (Optional): Users have the option to enable control access for the token.
Safe state reset (Optional): Users should indicate whether the access token should allow or disallow a safe state reset.
UID access: Users can select specific UIDs (like meters and inverters) which can be accessed by the token.
Request limit: Users have the ability to set a limit on the number of requests that can be made using the access token. By specifying a numerical value, users can control the maximum number of requests. Setting the limit to 0 will remove the limit. Keep in mind that by default the total number of request per device is 10.000 requests per day.
By providing these necessary inputs, users can successfully add a new access token with custom settings and access permissions for their devices.
![]() |
Third party access
This feature is only available for Embion EMS Controllers. |
Within the third party access feature, users can manage third-party access to their devices. These third parties can use the public API to monitor and/or control the device if access is granted.
Third parties can be granted monitoring and/or control access to the device. Monitoring access allows third parties to read data from the device, while control access enables them to send plant control commands to the device.
Only one third party with control access can be granted per device. There is no limit on third parties with monitoring access.
![]() |
Asset Status Check
This feature is only available for Embion EMS Controllers with software version 5.2.0 or above and a Dynamic, Pro, or Premium licence. |
The Asset Status Check tool allows users to manually test whether plant control commands can successfully control the assets (battery, PV, and EV charger) within their installation. This feature is useful for verifying that those assets can respond to control commands before setting up automated control rules.
![]() |
Command to Send
The command section allows you to configure and send instantaneous plant control commands to your device. Choose the values for each asset type you want to control and select how long you want the command to remain active.
Only the command options relevant to the connected assets are displayed. For example, if the plant has no battery connected, the battery setpoint slider will not be shown. |
Control Battery Setpoint: Controls the charging and discharging behaviour of your battery system. Positive values (1% to 100%) charge the battery at the specified percentage of maximum power. A value of 0% means no charging or discharging (idle). Negative values (-1% to -100%) discharge the battery at the specified percentage of maximum power.
Control PV Limit: Controls the power output of your solar inverters. A value of 100% means no power reduction (full output). Values from 1% to 99% reduce output to the specified percentage. A value of 0% means no power output (complete curtailment).
Control EV Limit: Controls the charging power of connected EV chargers. A value of 100% means no charging reduction (full charging speed). Values from 1% to 99% reduce charging to the specified percentage. A value of 0% means no charging allowed.
Duration: Select how long the command should remain active. Options are 5 minutes, 10 minutes, 15 minutes, or 1 hour. After the selected duration expires, the command will automatically be removed and the device will return to normal operation.
Status Display
Below the command section, the tool displays two status panels.
Plant control shows the current status for each control source: Energy pricing (control rules triggered by energy pricing conditions), Schedule (scheduled commands via API), and Instant (immediate commands including those from this tool). Each source can have one of the following statuses:
| Status | Description |
|---|---|
| Idle | No active command from this source |
| Pending | Command created but not yet sent to the device |
| Sent | Command sent to the device |
| Accepted | Device acknowledged the command |
| Active | Command is currently controlling the device |
| Rejected | Device rejected the command |
| Failed | Command failed to execute |
| Offline | Device is currently offline |
Instantaneous plant control command shows details when an instant command is active: the origin (shows "Asset Status Check" when sent from this tool), the current battery setpoint, PV limit, EV limit, and remaining duration countdown. When no command is active, this section shows "No command active".
Stopping an Active Command
When a plant control command is active (with status Active, Accepted, Sent, or Pending), a red Stop button appears next to the Send button. This allows you to immediately cancel the active command without waiting for it to expire.
Pressing the Stop button sends a neutral command to the device with the following values:
- Battery setpoint: 0% (idle)
- PV limit: 100% (full output)
- EV limit: 100% (full charging)
- Duration: 1 minute
This neutral command overrides the active command and restores the device to normal operation. After the 1-minute duration expires, the device will resume responding to other control sources (energy pricing rules, scheduled commands) as configured.
A confirmation dialogue is shown before the stop command is sent.
Requirements and Limitations
While an Asset Status Check command is active, the instant plant control channel is blocked. This means that other parties controlling your plant (such as aggregators) will not be able to send new instant commands until the current command expires or the device returns to idle. |
Commands sent via the Asset Status Check tool will override any other active plant control commands (from control rules or scheduled API commands) for the specified duration. |
To use the Asset Status Check tool, the following requirements must be met:
- The device must be an Embion EMS Controller with software version 5.2.0 or above
- The device must have a valid Dynamic, Pro, or Premium licence (to upgrade your licence, contact our sales team).
- The device must be online and connected to the internet
- You must have write permissions for devices in your EMS Site
Commands are duration-limited and will automatically expire. After expiration, the device returns to normal operation and will respond to other control sources (energy pricing rules, scheduled commands) as configured. |
Incidents & Event log
The Incidents & Event Log feature provides monitoring and diagnostics for connected devices and their assets. It can be accessed from the device menu by selecting "Incidents & Event Log".
This feature is only available for Embion EMS Controllers with software version 5.4.0 or above. |
Event Log
The Event Log shows a chronological record of state changes for a devices connected assets. It can be accessed by selecting the "Event Log" tab within the Incidents & Event Log view.
Each event displays the following information:
- Start Time: When the state change began.
- End Time: When the state change ended. If blank, the event is marked as Ongoing.
- Event Type: The category of the event.
- Status: The specific state reported by the asset.
- Asset Type: The type of asset (e.g., Energy meter, EV charger, Inverter PV, Inverter BESS, Inverter hybrid, or Auxiliary).
- Asset: The identifier of the specific asset.
- Data: Additional data associated with the event.
Three event types are tracked:
| Event Type | Possible Statuses |
|---|---|
| Operational State | Running, Warning, Error, Offline, Online (Unknown) |
| Setpoint Generation | Following setpoint for generation, Not following setpoint for generation |
| Setpoint Consumption | Following setpoint for consumption, Not following setpoint for consumption |
Events can be filtered by status using the dropdown filter at the top of the list. The list can also be refreshed by pressing the "Refresh" button.
![]() |
Incidents
Incidents are automatically created when connected assets (meters, EV chargers, etc.) report unusual behaviour, such as going offline or producing errors. When incidents are created or updated, notifications are sent to users (subject to their notification settings).
At the moment, no incidents will be created for PV inverters, since they usually switch off after sunset. |
Incident creation and updates will be delayed for assets that frequently report issues. |
Incident overview
The incident overview shows all incidents for a device. Each incident displays the following columns:
- ID: The unique identifier of the incident.
- Created at: When the incident was first detected.
- Resolved at: When the incident was resolved. Blank if the incident is still active.
- Severity: The highest severity of the issues within the incident. Possible values are Error, Warning, or Resolved.
- Issues: The number of issues within the incident.
- Status: Either Active (ongoing) or Resolved.
The overview can be filtered by status and severity using the dropdown filters.
![]() |
Incident details
Selecting an incident from the list opens the incident details view, which contains the following sections:
Incident Information displays the incidents ID, status, severity, issue count, creation date, and resolution date.
Affected assets shows each asset affected by the incident, along with its latest issue and severity. Each issue can be Ongoing or Recovered. Previous issues for the same asset are also visible under "Previous issues".
Event log shows the device events that are related to this specific incident.
![]() |
The system detects the following issue scenarios:
| Category | Ongoing | Recovered |
|---|---|---|
| Offline | Offline | Offline recovered |
| Warning | Warning | Warning recovered |
| Error | Error | Error recovered |
| Unknown | Unknown | Unknown recovered |
| Setpoint Generation | Not following setpoint | Setpoint recovered |
| Setpoint Consumption | Not following setpoint | Setpoint recovered |
Device settings
From the Devices overview page, you can view and edit the settings of a specific EMS controller. Press the three dots in the upper-right corner of the device you want to view. A pop-up listing the available device settings will appear.
Incorrect ETH settings can cause the device to become unreachable. |
![]() |
The displayed device settings are shown in the same language as the language settings on the device. |
Synchronise device
The synchronisation feature allows users to request and retrieve the live settings from the device, listing them for review and modification. If modified settings are already present on the device, a message will be displayed to notify the user.
Performing a synchronisation will remove any previously edited settings, if those are present. |
![]() | ![]() |
Edit Device Settings
Once a device is synchronised, users can proceed to edit its settings by using the “Edit” button. This action will open a new form that includes all the necessary inputs for modifying the settings.
![]() | ![]() |
Group settings
Users have the option to add a new empty group by pressing the “+ Group” button or make modifications to existing groups. Additionally, the clone button simplifies the process of duplicating groups when only minimal changes are required for creating a new group.
![]() | ![]() |
Priority settings
Several of the EMS Controller device settings let you assign a priority to a function in the form of a number that determines the order in which functions respond as a grid limit is approached, and as headroom returns.
![]() |
Two separate priority lists
The Embion EMS Controller keeps two independent priority lists: one protecting the import limit and one protecting the export limit. Each list has 10 slots, numbered 1 to 10, with priority 1 always the highest and priority 10 the lowest. A function is only ever part of one of the two lists (whichever limit it helps protect) and only occupies a slot once its priority has been configured.
not every slot needs to be filled. Only assets whose priority setting has been configured occupy a slot in the applicable list. |
![]() |
Which settings fill the slots
The following asset settings each claim a slot in one of the two priority lists:
- EV charger group > Set prio (import list)
- Heat pump group > Set prio (import list)
- Battery inverter group > Set charge prio (import list) and Set discharge prio (import list)
- Generator group > Import control priority (import list) and Export control priority (export list), only when the Generator control strategy is set to Start/Stop on Priority
- PV inverter group and battery-supported inverter group > Export control priority (export list)
- Generic asset control group > Select asset prio, assigned to either list depending on the configured Select asset control type
Because a battery has both a charge and a discharge setting, both occupy a slot on the import list; the discharge priority must always be set lower (more urgent) than the charge priority. |
Import priority list
On the import list, two kinds of functions are present: those that consume power (such as an EV charger or heat pump) and those that generate power or free up capacity (such as a generator or a discharging battery). As the import limit is approached, consuming functions are reduced starting with the lowest-priority function, working up towards priority 1, which is reduced last; generating functions respond in the opposite direction, increasing output starting with priority 1, working down towards the lowest priority. As headroom returns, both directions reverse: consuming functions are restored starting at priority 1, generating functions reduce output starting at the lowest priority.
![]() |
Export priority list
The export list only contains generating functions. As the export limit is approached, output is reduced starting with the lowest-priority function, working up towards priority 1; as headroom returns, output is restored in the opposite order.
![]() |
Discard or publish settings
After modifying and saving the Device settings, two buttons, “Discard” and “Publish,” will appear at the top of the form. Here are the actions associated with each button:
Discard: Using the “Discard” button will remove the modified settings and revert the form back to the settings that were originally requested during the last synchronisation with the device. This action allows users to discard any changes made and restore the previous settings.
Publish: Using the “Publish” button will publish the modified settings to the device. The changes will be automatically applied to the device if the automatic application option is selected. Alternatively, users can manually apply the changes on the device. The “Publish” action ensures that the modified settings take effect on the device.
These buttons provide users with flexibility and control over managing the modifications made to the Device settings. Users can either discard the changes or publish them to the device based on their preferences and requirements.
![]() | ![]() |
Settings published
When the modified settings are published to the device, the status section will provide users with information regarding the publishing process. It will indicate the progress of publishing and display any relevant messages or notifications. In case an error occurs during the publishing process, an error message will be shown, indicating that something went wrong and providing further details.
Additionally, after publishing the settings, the synchronise button will be disabled until the published settings are either applied or cancelled on the device. This ensures that the device and the remote settings are in sync before allowing further synchronisation actions.
![]() | ![]() |
Config Settings
The "config" or configuration settings cover the basic system settings for the plant.
Grid settings
These settings allow the user to define power and current limits for the plant. The following inputs are required to configure the grid settings:
- Grid current max (A)
- Grid + power max (kW)
- Grid - power max (kW)
- Limit per 15 min
- Expected baseline import load (%)
- Expected baseline export load (%)
![]() |
Grid current max
Enter the maximum allowed grid current for this plant. For example, if the main connection is 3x250 A, fill in 250.
This is typically the value of the main fuse. |
Grid + power max
Enter the maximum active power which might be consumed from the grid. For example: 50 kW.
Grid - power max
Enter the maximum active power which might be exported to the grid. For example: 100 kW. The Embion EMS Controller will implement export limitation controllers for configured solar inverters if the configured solar power exceeds the configured limit.
Limit per 15 min
This function is disabled by default. When enabled all power controllers (import and export) will use 15min values for control. The function can be enabled for only import or only export direction. This function is only of interest when the physical grid connection is significantly larger than the contracted power. When enabled, the system will unlock import and export power limits to the physical limit of the system, but will prevent the imported or exported energy to exceed the contracted power.
For a good prediction of the usage, a base load percentage should be given. This is the expected load when all controllable systems are off. The expected energy consumption is reserved during the 15 minutes.
Only use this function when the installation is capable of handling larger powers. If this function is not clear, leave this setting at its default “Disabled” state. |
Expected baseline import load (%)
Only used when Limit per 15 min is enabled for the import direction. Enter the expected baseline import load as a percentage of the contracted import power: the load still present when all controllable systems (PV curtailment, battery, EV chargers, etc.) are switched off. This baseline is reserved during each 15-minute interval so the import limit calculation isnt skewed by uncontrollable base load.
Expected baseline export load (%)
Only used when Limit per 15 min is enabled for the export direction. Enter the expected baseline export as a percentage of the contracted export power: the generation still present when all controllable systems are switched off. This baseline is reserved during each 15-minute interval so the export limit calculation isnt skewed by uncontrollable baseline generation.
Meter configuration
This section of the configuration settings allow the user to configure the connected meters (if any). Multiple groups can be made, where each group connects to the same type of meters, through the same physical interface. More information on creating and managing groups can be found here.
Make sure the meter active power orientation is in the right convention used within the Embion EMS Controller. |
When peakshaving for PV generation is active, the active power orientation for the grid meter should be correct. The Embion EMS Controller is only limiting (on grid power or grid current) the connected inverters when the measured grid power is negative (returning power to the grid). |
Configure meter group
The following inputs are required to configure a group consisting of one or more meters.
- Connection type
- Address range
- Meter type
- Meter IP address
- Meter TCP port
- Meter location
- Split solar/grid
- Override scaling factor
- Scale factor
- Assigned generator meter number
![]() |
The required inputs may vary, primarily (but not exclusively) depending on the selected Meter type and Connection type. |
Connection type
Select the connection type of the to be configured meter(s) the options are:
- RTU-A (X10)
- RTU-B (X11)
- RTU-C (X12)
- P1
- TCP/IP
When the meter connection type is P1, the only additional settings required are the number of connected P1 meters and meter location. |
Address range
Enter the address range of the meter(s) to be configured. Individual addresses can be separated using a comma (,), or a range can be defined using a hyphen (-). For example, the input 1,2,4-10 sets an address range from 1 to 10, excluding 3.
Each address may only be used once per RTU port. Meters and inverters can be connected to the same RTU port, provided that the baud rate settings are identical and each connected asset has a unique address. |
Meter type
The Embion EMS supports meters from a wide array of brands and types. Use the drop-down menu to select the brand or type of meter to be configured.
The support page of the Embion website has an extensive list of supported devices. |
Meter IP
Enter the IP address of the meter(s) to be configured. For example: “192.168.0.125”.
Multiple meter addresses can be defined using an address range, or a single IP address can be entered if all addresses are reachable via the same TCP/IP server.
If all assets are reachable at the same meter address but use different IP addresses, a single address can be entered together with an IP address range.
If each meter address has its own TCP/IP server and a dedicated IP address, an IP range can be entered. To define a range, enter the first IP address, followed by a comma (,) or a hyphen (-) and the last octet of the final IP address.
For example, if the address range is set to 1–4 (or 1, 2, 3, 4) and each address has a dedicated IP address, the IP input can be 192.168.0.10-13 (or 192.168.0.10, 11, 12, 13). The Embion EMS Controller will translate this into the following IP addresses: 192.168.0.10, 192.168.0.11, 192.168.0.12, and 192.168.0.13.
The meter IP address is only required when the meter connection type is set to TCP/IP.
When multiple IP addresses are defined, the number of configured meter addresses must be either one or match the number of configured IP addresses. Otherwise, an error will occur when applying the settings. |
Meter TCP port
Enter the port number of the meter(s) to be configured. For example: “502”.
The port number is only required when the meter connection type is set to TCP/IP.
Meter location
Select here the meter(s) location of the to be configures meter(s), options are:
- Grid meter
- Load meter
- Solar meter
- Generator meter
- Wind meter
- MLOEA-PAP
- MLOEA-SAP
- MLOEA-TAP
The Grid meter is used for control. To make sure the readout speed is not limited it is good practice to connect the Grid meter to a un-used port (RTU-A, RTU-B, RTU-C), and connect other devices to other ports. On this way the maximum readout speed is reached. The solar, generator and wind meter can be used to measure power and energy flows from assets which can not be connected directly. The measurement direction should be the same as for consuming loads. Therefore the measured active power should be negative when there is generation. For a MLOEA grid connection, all meters (MLOEA-PAP, MLOEA-SAP and optionally the MLEOA-TAP) need to be configured. The Embion EMS Controller will calculate the actual grid power and currents by combining all meters. The MLOEA meters will replace the grid meter, configuring both will result in an incorrect configuration. Setting up only one of the minimum of two MLOEA meters result in an incorrect configuration.
Split solar/grid (only for load meters)
This option is available when a load meter is selected. Enabling this function creates two additional meter registers: one for energy directly consumed from solar energy and one for energy directly consumed from grid energy. Two system configurations are supported:
- System with at least one grid meter and one or more load meters: All energy measured by the grid meter is counted as grid energy. Any energy consumed by the load meters that is not sourced from the grid meter is counted as solar energy.
- System without a grid meter: The power delivered by the connected solar inverters is used to calculate solar energy. All remaining energy consumption is counted as grid energy.
Activation of the split solar/grid energy meters requires at least one configured grid meter or one configured solar inverter. If neither is present, an error will be raised during settings activation. |
Override scaling factor (only for P1 meters)
The values read from the P1 meter can be scaled using a fixed scaling factor. The default scaling factor is 1x. If Yes is selected, the user is prompted to enter the scaling factor.
Only change the default scaling factor if required by the grid operator. Selecting an incorrect value may result in inaccurate energy measurements and improper control of active power. |
Scale factor
This option is only available when Override scaling factor is set to Yes. Select the desired scaling factor:
- 1x (default)
- 40x
- 60x
- 80x
- 200x
- 500x
- 2000x
- 2500x
- 12000x
Verify the scaling factor carefully. Selecting an incorrect value may result in inaccurate energy measurements and improper control of active power. |
Assined generator meter number
Only shown when Meter location is set to Generator meter. When multiple generators are configured, each one needs its own dedicated meter. Enter a number here to identify which generator this meter measures, then enter the same number in the "Assigned generator meter number" field of that generators group.
Inverter configuration
This section allows the user to set up the connected inverters, if any. Multiple groups can be created, with each group connecting to the same type of inverters through the same physical interface. More information on creating and managing groups can be found here.
Configure inverter group
The configuration of an inverter group requires the following inputs:
- Connection type
- Address range
- Inverter type
- Inverter IP
- Inverter TCP port
- Strings per inverter
- Total number of solar panels
- Peak power per panel
- Total group PV power (AC)
- Export control priority
- Enable active power control
![]() |
When the inverter has battery support, the following extra fields are required:
- Maximum active battery power
- Battery energy capacity (Capacity of battery, should be the same for all batteries in the group), used for weighted SoC average.
- Set charge prio
- Set discharge prio
- Minimum SoC (State of Charge)
- Maximum SoC
- Minimum SoC for remote control
- Minimum SoC for consumption compensation
- Maximum SoC for non-solar charge
- Allow automatic charge
![]() |
The required inputs may vary, primarily (but not exclusively) depending on the selected inverter type and Connection type. |
Connection type
The following connection types are available:
- RTU-A (X10)
- RTU-B (X11)
- RTU-C (X12)
- TCP/IP
Address range
Enter the address range of the inverter(s) to be configured. Individual addresses can be separated using a comma (,), or a range can be defined using a hyphen (-). For example, the input 1,2,4-10 defines an address range from 1 to 10, excluding 3.
Each address may only be used once per RTU port. Meters and inverters can be connected to the same RTU port, provided that the baud rate settings are identical and each connected asset has a unique address. |
Inverter type
The Embion EMS supports inverters from a wide array of brands and types. Use the drop-down menu to select the brand or type of meter to be configured.
The support page of the Embion website has an extensive list of supported devices. |
Inverter IP
Enter the IP address of the inverter(s) to be configured. For example: “192.168.0.125”.
Multiple inverter addresses can be defined using an address range, while a single IP address can be entered if all addresses are reachable via the same TCP/IP server.
If all servers are reachable at the same inverter address but use different IP addresses, a single address can be entered together with an IP address range.
If each inverter address has its own TCP/IP server and a dedicated IP address, an IP range can be entered. To define a range, enter the first IP address, followed by a comma (,) or a hyphen (-) and the last octet of the final IP address.
For example, if the address range is set to 1–4 (or 1, 2, 3, 4) and each address has a dedicated IP address, the IP input can be 192.168.0.10-13 (or 192.168.0.10, 11, 12, 13). The Embion EMS Controller will translate this into the following IP addresses: 192.168.0.10, 192.168.0.11, 192.168.0.12, and 192.168.0.13.
The inverter IP address is only required when the inverter connection type is set to TCP/IP.
When multiple IP addresses are defined, the number of configured addresses must be either one or match the number of configured IP addresses. Otherwise, an error will occur when applying the settings. |
Inverter TCP port
Enter the port number of the inverter(s) to be configured. For example: “502”.
The port number is only required when the inverter connection type is set to TCP/IP.
Strings/MPPT per inverter
Enter the number of individual strings or MPPT data points to be read for each inverter in the group. This corresponds to the number of strings or MPPTs that are individually monitored per inverter.
Total number of solar panels
Enter the total number of solar panels installed for this inverter group.
Peak power per panel
Enter the peak power per panel (Wp) for the installed solar panels. The total solar power, calculated as number of installed panels × peak power per panel, is used to determine the required export limit controllers. If different panel types are installed, ensure that the calculated total solar power (number of installed panels × peak power per panel) accurately reflects the installation.
Total group PV power (AC)
The total sum of the nominal output (AC) power of all the inverters configured in the group.
Export control priority
Sets the priority of this inverter group when the output needs to be reduced because an export limit is reached. When power must be curtailed, the Embion EMS Controller reduces groups according to their priority, with lower-priority groups (higher numbers) reduced first and higher-priority groups (lower numbers) reduced last. This applies to both PV inverter groups and battery-supported inverter groups.
More information on how priorities work can be found here.
Enable active power control
When this setting is disabled, the inverter is not controlled for active power. If required, certain inverter groups can be excluded from active power control while other groups have the control enabled.
The system controlled by the Embion EMS Controller must accept external control signals. To enable this, the external logger must be configured correctly. Active power control on the external logger must be disabled, and the logger must be configured to accept external power control commands. |
Maximum active battery power
This setting is only displayed when an inverter with battery support is selected. The maximum active power of the battery can be specified. The Embion EMS Controller limits the battery power setpoint to the configured value. The charge and discharge setpoints sent to the battery will not exceed this limit.
The limit is applied per controlled battery. If multiple batteries are controlled within a group, the configured limit applies to each battery individually.
Battery energy capacity
Specifies the capacity of each battery. This value is used for the weighted state-of-charge (SoC) calculation. If multiple batteries are controlled within a single group, the specified value applies to each battery individually.
Set charge prio
Set the charge priority of the battery. Like other consuming assets, batteries with a lower-numbered (higher) charge priority are reduced last as the import limit is approached and restored first as headroom returns; once its priority allows charging, a charge setpoint is issued to the battery. The charge priority should be a higher number (lower priority) than the discharge priority.
More information on how priorities work can be found here.
Set discharge prio
Set the discharge priority of the battery. Like the generator, batteries with a lower-numbered (higher) discharge priority start discharging first as the import limit is approached and stop discharging last as headroom returns; while active, the battery discharges at maximum power, which can be used for peak shaving to prevent exceeding grid limits. The discharge priority should be a lower number (higher priority) than the charge priority.
More information on how priorities work can be found here.
Minimum SoC
Set the minimum allowed state of charge (SoC). When this SoC is reached, the battery power setpoint prevents further discharge. If the measured SoC falls below the minimum, the battery is automatically charged according to the configured charge priority until the minimum SoC is restored.
Maximum SoC
Set the maximum allowed state of charge (SoC). When this SoC is reached, the battery power setpoint prevents further charging.
Minimum SoC for remote control
Specify the minimum state of charge (SoC) to which the battery can be discharged via remote control. This value must be equal to or higher than the configured Minimum SoC. The difference is used solely to compensate for the grid import limit using the battery.
When generation control is set to maximum via the public API or HUB, the battery will discharge until this SoC is reached. However, when the battery discharges due to remotely set grid limits (via public API or HUB), the discharge is not restricted by this value.
Minimum SoC for consumption compensation
Specify the minimum SoC to which the battery can be discharged during own consumption compensation. (This function must be enabled in the Active Power Control settings.)
Maximum SoC for non-solar charge
Specify the maximum SoC for all charging actions, except when charging with negative grid power. This value must be equal to or lower than the configured Maximum SoC. The difference can only be charged if Charge with Negative Grid Power is enabled and the grid power is negative.
Allow automatic charge
When this setting is enabled, the battery will receive a charge setpoint as soon as the priority allows. When disabled, the Embion EMS Controller will not automatically charge the battery, except when consumption is set to maximum or Charge Battery with Grid Return Power is enabled.
If this function is used in combination with own consumption compensation, the Maximum SoC for Non-Solar Charge must be at least 2% lower than the Minimum SoC for Consumption Compensation.
EV charger configuration
This section allows the user to set up the connected EV chargers, if any. Multiple groups can be created, with each group connecting to the same type of EV chargers through the same physical interface. More information on creating and managing groups can be found here.
Note on EV chargers with type "EVBox":
When creating a group of EV chargers with type ‘EVBox’, only one group per RS485 port can be created.
When modifying a group of EV chargers of type EVBox, the historical data of the EVBox chargers may become inaccurate due to limitations in the EVBox protocol.
Configure EV charger group
The configuration of an EV charger group requires the following inputs:
- Charger type
- Charger connection
- Amount of chargers
- Amount of zones
- Amount of chargers per zone
- Address range
- Min. charge current (A)
- Max. charge current (A)
- Min. charge power (kW)
- Max. charge power (kW)
- Amount of Sockets
- Set prio
- Charger IP
- Charger TCP port
- Limit per group
- Group current limit (A)
- Device username
- Device password
- Device SN
![]() | ![]() |
The required inputs may vary, primarily (but not exclusively) depending on the selected charger type and charger connection. |
Charger type
The Embion EMS supports EV chargers from a wide array of brands and types. Use the drop-down menu to select the brand or type of EV charger to be configured.
The support page of the Embion website has an extensive list of supported devices. |
Charger connection
The following connection types are available:
- RTU-A (X10)
- RTU-B (X11)
- RTU-C (X12)
- TCP/IP
- REST API
Amount of chargers
Enter the amount of EVBox chargers (both EVBox Hub and EVBox Satellite) connected to the physical RS485 interface.
Amount of zones
Enter the amount of zones configured in the Schneider EcoStruxure EV Charging Expert
Amount of chargers per zone
Enter the amount of chargers added to single zone in the Schneider EcoStruxure EV Charging Expert. When multiple zones are configured, the amount of chargers per zone should be the maximum number of chargers per zone.
Address range
Enter the address range of the charger(s) to be configured. Individual addresses can be separated using a comma (,), or a range can be defined using a hyphen (-). For example, the input 1,2,4-10 defines an address range from 1 to 10, excluding 3.
Min. charge current (A)
Select the minimum charge current that is sent to the EV-charger(s) during import limitation. If this value is greater than 0, the charger will not stop charging, even if the configured import limit is exceeded. The configured minimum charge current must be less than or equal to the maximum charge current.
Max. charge current (A)
Select the maximum charge current that is sent to the EV-charger(s) when no import limit is applied. The configured minimum charge current must be less than or equal to the maximum charge current.
Min. charge power (kW)
Select the minimum charge power that is sent to the EV-charger(s) during import limitation. If this value is greater than 0, charging will continue, even if the configured import limit is exceeded. The configured minimum charge power must be less than or equal to the maximum charge power.
Max. charge power (kW)
Select the maximum charge power that is sent to the EV-charger(s) when no import limit is applied. The configured minimum charge power must be less than or equal to the maximum charge power.
Amount of Sockets
For a charger with multiple sockets, the amount of sockets per charger can be defined.
For example: A single Hypercharger can have 1, 2 or 3 sockets, depending on the physical configuration. The amount of sockets should be filled in.
When there are physical differences between the chargers, for instance 1 charger with 2 sockets and 1 charger with 3 sockets, these chargers should be configured in separate groups.
Exceptions: For some integrations, we only connect to the Power Unit. In this case the total amount of sockets connected to the Power Unit should be configured.
Set prio
The priority of the EV charger current/power can be configured. When power is available for consumption, the Embion EMS Controller increases loads according to their priority, with higher-priority loads (lower numbers) being released first and reduced last. An EV charger with priority 1 always has at least the minimum charge current available and, when system limits allow, its current is increased up to the maximum charge current. Any other EV chargers with priority 2 or higher also have the minimum charge current available, but their current is only increased if system limits allow it and all chargers with a lower priority number are fully released.
More information on how priorities work can be found here.
Charger IP
Enter the IP address of the charger(s) to be configured. For example: “192.168.0.125”.
Multiple charger addresses can be defined using an address range, while a single IP address can be entered if all addresses are reachable via the same TCP/IP server.
If all servers are reachable at the same charger address but use different IP addresses, a single address can be entered together with an IP address range.
If each charger address has its own TCP/IP server and a dedicated IP address, an IP range can be entered. To define a range, enter the first IP address, followed by a comma (,) or a hyphen (-) and the last octet of the final IP address.
For example, if the address range is set to 1–4 (or 1, 2, 3, 4) and each address has a dedicated IP address, the IP input can be 192.168.0.10-13 (or 192.168.0.10, 11, 12, 13). The Embion EMS Controller will translate this into the following IP addresses: 192.168.0.10, 192.168.0.11, 192.168.0.12, and 192.168.0.13.
The charger IP address is required only when the charger connection type is set to TCP/IP or when using a local REST API.
When multiple IP addresses are defined, the number of configured addresses must be either one or match the number of configured IP addresses. Otherwise, an error will occur when applying the settings. |
Charger TCP port
Enter the port number of the charger(s) to be configured. For example: “502”.
The port number is only required when the charger connection type is set to TCP/IP.
Limit per group
This setting limits the total output current of the group. So the total combined setpoint send to the chargers in this group, will be limited by Group current limit.
Group current limit
The total current limit the group will be limited to when above setting is enabled.
Device username
Enter the username of the to be configured EV Charger(s).
Device password
Enter the password of the to be configured EV Charger(s).
Device SN
Enter the serial number (SN) of the to be configured EV Charger.
Heat pump configuration
This section allows the user to set up connected heat pump(s), if any. Multiple groups can be created, with each group connecting to the same type of heat pump through the same physical interface. More information on creating and managing groups can be found here.
Configure heat pump group
The configuration of a heat pump group requires the following inputs:
- Heat pump connection
- SG ready version
- Set prio
![]() |
Which inputs are required depends on the selected heat pump connection. |
Heat pump connection
Select the connection type of the to be configured heat pump(s) the options are:
- I/O (SG_ready)
- RTU-A (X10)
- RTU-B (X11)
- RTU-C (X12)
- TCP/IP
SG ready version
Select the SG_ready version of the to be configured heat pump(s) the options are:
- Version 1.0
- Version 1.1
Set prio
The priority of the heat pump can be configured. As the import limit is approached, loads are reduced starting with the lowest-priority (highest-numbered) load; a heat pump with priority 1 is reduced last. As headroom becomes available again, loads are released in the opposite order, starting with the highest-priority (lowest-numbered) load; a heat pump with priority 1 is released first.
More information on how priorities work can be found here.
Generator configuration
This section allows the user to set up the connected generators, if any. Multiple groups can be created, with each group connecting to the same type of generators through the same physical interface. More information on creating and managing groups can be found here.
Configure generator group
The configuration of a generator group requires the following inputs:ollowed by a comma (,) or a hyphen (-) and the last octet of the final IP address.
- Generator type
- Connection type
- Address range
- Generator IP address
- Generator TCP port
- Assigned analogue output number
- Assigned external output number
- Assigned generator meter number
- Minimum generator power (kW)
- Maximum generator power (kW)
- Generator rated power (kW)
- Generator control strategy
- Import control priority
- Export control priority
- Generator start SoC (%)
- Generator stop SoC (%)
- Generator control
![]() |
The required inputs may vary, primarily (but not exclusively) depending on the selected Generator type and Connection type. |
Generator type
The Embion EMS supports generators from a wide array of brands and types. Use the drop-down menu to select the brand or type of generator to be configured.
To see which assets are supported, the support page of the Embion website has an extensive list of supported devices. |
Connection type
Select the connection type of the to be configured generator(s), the options are:
- RTU-A (X10)
- RTU-B (X11)
- RTU-C (X12)
- TCP/IP
Address range
Enter the address range of the generator(s) to be configured. Individual addresses can be separated using a comma (,), or a range can be defined using a hyphen (-). For example, the input 1,2,4-10 sets an address range from 1 to 10, excluding 3.
Generator IP address
Enter the IP address of the generator(s) to be configured. For example: "192.168.0.125".
Multiple generator addresses can be defined using an address range, or a single IP address can be entered if all addresses are reachable via the same TCP/IP server.
If all assets are reachable at the same generator address but use different IP addresses, a single address can be entered together with an IP address range.
If each generator address has its own TCP/IP server and a dedicated IP address, an IP range can be entered. To define a range, enter the first IP address, followed by a comma (,) or a hyphen (-) and the last octet of the final IP address.
For example, if the address range is set to 1–4 (or 1, 2, 3, 4) and each address has a dedicated IP address, the IP input can be 192.168.0.10-13 (or 192.168.0.10, 11, 12, 13). The Embion EMS Controller will translate this into the following IP addresses: 192.168.0.10, 192.168.0.11, 192.168.0.12, and 192.168.0.13.
The generator IP address is only required when the connection type is set to TCP/IP.
When multiple IP addresses are defined, the number of configured generator addresses must be either one or match the number of configured IP addresses. Otherwise, an error will occur when applying the settings. |
Generator TCP port
Enter the port number of the generator(s) to be configured. For example: "502".
The port number is only required when the connection type is set to TCP/IP.
Assigned analogue output number
Enter the analogue output channel number used to send the generators control setpoint (for example a throttle or governor signal). This number must correspond to an output number configured in the Auxiliaries section.
Assigned external output number
Enter the digital output channel number used to start and stop the generator, for example wired to a start/stop relay. This number must correspond to an output number configured in the Auxiliaries section.
Assigned generator meter number
Enter the number identifying which configured meter (with Meter location set to Generator meter) measures this generators output.
Minimum generator power (kW)
Enter the minimum power output of the generator. If this value is greater than 0, the generator will not stop, even if the requested output falls below this value.
Maximum generator power (kW)
Enter the maximum power output the Embion EMS Controller is allowed to request from the generator.
Generator rated power (kW)
Enter the rated (nameplate) power of the generator. This value is used by the Embion EMS Controller to determine the available generator capacity.
Generator control strategy
- Start/Stop on SoC: the generator starts and stops automatically based on the battery state of charge, using the Generator start SoC and Generator stop SoC settings below.
- Start/Stop on Priority: the generator is started and stopped based on its Import control priority and Export control priority settings below, in the same way as other prioritised assets.
Import control priority
Only used when Generator control strategy is set to Start/Stop on Priority. Sets the priority of the generator when power is needed to cover consumption (import limit reached). Lower numbers are higher priority. As the import limit is approached, generators are started starting with the highest-priority (lowest-numbered) generator first. As the generator is no longer needed, generators are stopped in the opposite order, starting with the lowest-priority (highest-numbered) generator; a generator with priority 1 stops last. This is the reverse of how consuming assets (EV chargers, heat pumps) respond to the same import limit (those are reduced starting at the lowest priority and restored starting at the highest priority).
More information on how priorities work can be found here.
Export control priority
Only used when Generator control strategy is set to Start/Stop on Priority. Sets the priority of the generator when its output needs to be reduced because an export limit is reached. Lower numbers are higher priority.
More information on how priorities work can be found here.
Generator start SoC (%)
Only used when Generator control strategy is set to Start/Stop on SoC. Sets the battery state of charge at which the generator starts.
Generator stop SoC (%)
Only used when Generator control strategy is set to Start/Stop on SoC. Sets the battery state of charge at which the generator stops. Generator start SoC and Generator stop SoC form a hysteresis band, to prevent the generator from starting and stopping repeatedly.
Generator control
When disabled (default), the Embion EMS Controller will not automatically start or stop the generator. When enabled, the controller starts and stops the generator according to the configured Generator control strategy.
Auxiliary configuration
This section of the configuration settings allow the user to configure auxiliary devices (if any). Multiple groups can be made, where each group connects to the same type of auxiliary device, through the same physical interface. More information on creating and managing groups can be found here.
Configure Auxiliary group
Configuration of a group of auxiliary devices requires the following inputs:
- Auxiliaries type
- Auxiliaries connection
- Address range
- ao0 assigned analogue output number
- ao0 output type
- do0 assigned external output number
- do1 assigned external output number
- do2 assigned external output number
- do3 assigned external output number
- di0 assigned external input number
- di1 assigned external input number
- di2 assigned external input number
- di3 assigned external input number
- Invert output
- Auxiliaries IP
- Auxiliaries TCP port
![]() | ![]() |
The required inputs may vary, primarily (but not exclusively) depending on the selected Auxiliaries connection and Auxiliaries type. |
Auxiliaries type
The Embion EMS supports auxiliary devices from a wide array of brands and types. Use the drop-down menu to select the brand or type of auxiliary device to be configured. Apart from the devices the user can also select "controllable load". See next section for more information about that setting.
To see which assets are supported, the support page of the Embion website has an extensive list of supported devices. |
If a pyrano sensor connected to the Huawei smartlogger is configured, use the configured pyrano sensor address configured in the smartlogger. |
Auxiliaries connection
Select the connection type of the to be auxiliary device(s) the options are:
- RTU-A (X10)
- RTU-B (X11)
- RTU-C (X12)
- Modbus TCP/IP
Auxiliaries slaves
Enter the address range of the auxiliary devices to be configured. Individual addresses can be separated using a comma (,), or a range can be defined using a hyphen (-). For example, the input 1,2,4-10 sets an address range from 1 to 10, excluding 3.
ao0 assigned analogue output number
This setting links the auxiliary devices analogue output to a matching Generic Asset Control group. Enter a number here, then create (or select) a Generic Asset Control group with Control type "Auxiliary Analogue output" and enter the same number in its "Assigned analogue output number" field. The two numbers must match for the output to be controlled.
ao0 output type
Select the signal type of the analogue output:
0-20mA / 0-10V 4-20mA
do0 – do3 assigned external output number
Enter the number identifying this digital output channel. This number is used to link the channel to a GPIO control rule: in <#hub_deviceSettings_configSettings_gpioSettings> GPIO control, select "Auxiliary External Output" and enter the same number in "Assigned external output number" to control this specific digital out (do) channel.
di0 – di3 assigned external input number
Enter the number identifying this digital input channel. This number is used to link the channel to a GPIO control rule: in <#hub_deviceSettings_configSettings_gpioSettings> GPIO control, select "Auxiliary External Input" and enter the same number in "Assigned external input number" to monitor this specific digital in (di) channel.
Invert output
When enabled, this feature inverts the values on the digital output port of the IO-tM-DA1P1R1. This is the port used by the do0 assigned external output number setting.
Auxiliaries IP
Enter the IP address of the auxiliary device(s) to be configured. For example: "192.168.0.125".
Multiple auxiliary device addresses can be defined using an address range, or a single IP address can be entered if all addresses are reachable via the same TCP/IP server.
If all assets are reachable at the same auxiliary device address but use different IP addresses, a single address can be entered together with an IP address range.
If each auxiliary device address has its own TCP/IP server and a dedicated IP address, an IP range can be entered. To define a range, enter the first IP address, followed by a comma (,) or a hyphen (-) and the last octet of the final IP address.
For example, if the address range is set to 1–4 (or 1, 2, 3, 4) and each address has a dedicated IP address, the IP input can be 192.168.0.10-13 (or 192.168.0.10, 11, 12, 13). The Embion EMS Controller will translate this into the following IP addresses: 192.168.0.10, 192.168.0.11, 192.168.0.12, and 192.168.0.13.
When multiple IP addresses are defined, the number of configured auxiliary device addresses must be either one or match the number of configured IP addresses. Otherwise, an error will occur when applying the settings. |
Auxiliaries TCP port
Enter the port number of the auxiliary device(s) to be configured. For example: "502".
The port number is only required when Auxiliaries connection is set to TCP/IP.
Active power control
By default, the configured number and power of the solar panels, together with the configured maximum grid export power and maximum grid current, allow the Embion EMS Controller to determine whether an active power controller and/or a current controller is required for the installation.
Configuration of the Active power control requires the following inputs:
- Power control
- Safety margin (kW)
- Control speed
- Low Power Limit
- Total PV inverter power
- Set minimum PV power limit to 5%
- Force battery charge before PV reduction
- Max. power limit %
- Allow PV for import limit
- Charge battery with grid return power
- Compensate own usage with battery
- Radiation check
![]() | ![]() |
The exact required inputs may vary, primarily depending on the selected type of Power control. |
Power control
A plant control active power controller is enabled by default. The user can modify this default behaviour by changing the Active power control setting.
- Auto (default): Depending on the configured limits, an active power controller and/or a grid current controller is enabled automatically.
- Force disable: All power controllers are disabled. Plant control, export limit control, and grid voltage control are not available. Use this setting with caution.
- Force enable: Plant control, active power control, and grid current control are enabled regardless of the configured solar power. When using this setting, the maximum reduction value can be limited by the user.
Setting the “Force disable” option will disable all active power controllers. There will be no grid current, power or voltage control done by the Embion EMS Controller. Also power control via plant control is disabled! Therefore inverters will not be limited when EPEX price control is active. |
Safety margin (kW)
The Safety margin is set to 0 by default and applies a positive offset to the configured grid return power. For example, if a plant is not allowed to return power to the grid (negative grid power), the maximum grid return power is set to 0 kW. In practice, however, power may still be exported briefly when loads are switched off. To prevent this, a safety margin can be configured.
The Embion EMS Controller offsets the control setpoint by the configured safety margin. If the grid return power is set to 0 kW and the safety margin is set to 5 kW, the controller will limit PV and battery power such that the grid power target is +5 kW. If a 4 kW load is suddenly switched off, the grid power will remain positive, and the Embion EMS Controller will automatically correct for the change.
Only use the Safety margin option in situations where a very strict no-export policy applies. Enabling a safety margin increases total grid power consumption and therefore leads to higher energy costs. |
Control speed
The Control speed is set to Normal by default. This setting defines the overall speed at which the internal control loops operate and how the assets are controlled. If a faster system response is required, the control speed can be increased.
When using the Fast option, all connected assets must have sufficient response speed and be able to follow setpoints within a maximum of 1 second. Assets that do not meet this requirement may destabilise the system. |
Low power limit
When enabled, a minimum reduction value of 5% is sent to all PV inverters, ensuring that they continuously generate 5% of their nominal power. This option is disabled by default and is required by some inverter brands or specific installations.
Total PV inverter power (kW)
The sum of the total nominal PV inverter power. Inverters that are used only as battery converters should not be included in this sum.
Set minimum PV power limit to 5%
When enabled, the PV inverters are prevented from being reduced below 5% of their nominal power, ensuring a minimum generation floor of 5% is always maintained.
Force battery charge before PV reduction
When enabled, the Embion EMS Controller will prioritise maximising battery charging power before reducing PV generation. However, this may affect the system’s response time if one or more battery systems are not capable of charging at the required rate.
Maximum power limit
Setting the maximum power limit to less than 100% restricts the PV inverters maximum output power to the configured percentage. As a result, the inverters will never reach their full output power, even if the grid current and grid return power limits have not yet been reached.
Allow PV for import limit
This setting is disabled by default. When enabled, it allows the PV limit controller to increase PV power — overruling other active power control rules, such as a reduction requested by an aggregator — whenever doing so is needed to prevent the import limit from being exceeded. This means PV generation can continue at some level, rather than being reduced to its minimum output. This override behaves as a function with priority 1: it is handled simultaneously with, and proportionally to, any other asset groups that are also configured with priority 1, if any.
Charge battery with grid return power
When this function is enabled, the battery charging power is increased whenever the mains active power becomes negative, allowing returned grid power to be used for charging the battery. It is recommended to disable the “Allow automatic charge” option in the inverter group when using this function.
Compensate own usage with battery
When this function is enabled, the battery will discharge whenever power is drawn from the grid, helping to reduce grid consumption. The minimum state of charge (SoC) to which the battery can be discharged is configured individually for each battery inverter.
Radiation check
When Zonbalans is configured with a pyranometer sensor, this setting is available.
ZonBalans by Enexis is a smart service for business customers that enables them to feed solar energy back into the grid, even when the electricity grid is congested. |
If enabled, the controller compares the measured irradiance from the pyranometer sensor with the actual PV output power. If a significant deviation is detected over a longer period, an error is triggered and the PV output is reduced.
This function is used to detect a defective or contaminated pyranometer sensor.
GPIO control
GPIO control lets you define custom rules that react to the state of a digital input or a comparison against a numeric value, and set an output in response. Each rule is built from a trigger (what the rule watches) and an action (what the rule does when triggered). Which fields appear depends on which GPIO you select.
![]() |
GPIO control contains the following (possible) settings:
- Select GPIO
- If becomes
- Then set
- Set to
- When
- Operator
- Value
- Set value
- Multi input
- Assigned external output number
- Assigned external input number
Select GPIO
The input or output this rule applies to: IN1, IN2, Auxiliary External Input, OUT1, OUT2, or Auxiliary External Output. Choosing IN1, IN2, or Auxiliary External Input builds a state-based rule; choosing OUT1, OUT2, or Auxiliary External Output builds a value-comparison rule. The fields below change accordingly.
If becomes
The state the selected input must reach for this rule to trigger: High or Low
Then set
Select the action this rule performs once triggered:
Disable battery charge / Disable battery discharge / Disable battery completely Export limit / Minimise generation / Minimise consumption OUT1 / OUT2 / Auxiliary External Output (sets the selected digital output, paired with Set to below).
Assigned external input number
Enter the Auxiliary input channel number to monitor, when Select GPIO is set to Auxiliary External Input. Corresponds to the input numbers configured in the Auxiliaries section.
Set to
Select the state to apply to the output chosen in Then set: True or False.
When
Select the value this rules condition compares: Battery SoC, Battery power, Grid power, Solar power, Total load meter power, PRIO, Actual max grid current, Control generation, Control consumption, or Reduction.
Operator
Select how the value in When is compared against Value: Greater than, Less than, Equal to, or Not equal to.
Value
Select the value to compare against. Min, Nom, and Max use a preset limit for whatever was selected in When; the custom option lets you enter your own number in Set value below.
Set value
Enter the number to compare against, when a custom Value is selected above.
Multi input
Select whether this rule uses a single condition or combines more than one: Single, AND, or OR.
Assigned external output number
Enter the Auxiliary output channel number to control, when Select GPIO is set to Auxiliary External Output. Corresponds to the output numbers configured in the Auxiliaries section.
Generic asset control
Using Generic asset control, different generic loads or generation units can be controlled. The configuration of a Generic asset control group requires the following inputs:
- Control type
- Assigned analogue output number
- Selected modbus register
- Maximum power for asset (kW)
- Select asset prio
- Select asset control type
The required inputs may vary, depending on the selected Control type. |
![]() |
Control type
The following control types can be selected:
- Auxiliary Analogue output: An analog output module can be added in the Auxiliaries section. The output of the module is controlled based on the settings set in this group.
- Embion Modbus server register: A dedicated register on the Embion Modbus server will be assigned to this group. The output of this group will be available in the selected register.
To use the Embion Modbus server register control type, the Modbus TCP Server must be configured. See: TCP configuration
Assigned analogue output number
The group can be assigned to an output group number when the control type Analog output group is selected. The output group number should correspond to an output number assigned in the Auxiliaries section.
Selected modbus register
The group can be assigned to a Modbus Server register when the control type Embion Modbus server register is selected. The register number corresponds to one of the 10 dedicated modbus registers which are specified in the Modbus interface.
Maximum power for asset (kW)
The maximum output power of the assigned assets in this group.
Select asset prio
The priority of this group can be set here. To which range of priorities the group is assigned is determined by the setting “Select asset control type”.
More information on how priorities work can be found here.
Select asset control type
The priority of this group can be used in two different cases:
- Import (default): The priority is taken in to respect to the EV prio, Charge and Discharge Prio of a battery supported inverter group and the output is controlled when import limits are reached
- Export: The priority is taken in to respect to “Set export control prio” of an inverter group with PV support and the output is controlled when export limits are reached
Grid voltage control
The Grid voltage control can be enabled to apply an active power controller in the Embion EMS Controller, regulating the measured grid voltage. The controller monitors the maximum line-to-neutral voltage of the grid. If this voltage exceeds the configured maximum grid voltage, the PV inverter active power setpoint is reduced using a fixed PI controller. This limits the active power and helps lower the grid voltage.
![]() |
Grid Voltage Control contains the following (possible) settings:
- Enable grid voltage control
- Max grid voltage
- U1 voltage
- U2 voltage
Enable grid voltage control
Select the grid voltage control strategy to apply. Three options are available:
- Disable (default): grid voltage control is switched off; the Embion EMS Controller does not monitor or act on grid voltage.
- Max voltage regulation: applies the fixed PI controller described above — active power is reduced whenever the measured grid voltage exceeds the configured Max grid voltage.
- Linear voltage export control: Limits the export power along a linear curve between the U1 voltage and U2 voltage thresholds (export power is unrestricted below U1 voltage and reduced to zero once the grid voltage reaches U2 voltage).
![]() |
Max grid voltage
Sets the line-to-neutral voltage threshold used by Max voltage regulation. When the measured grid voltage exceeds this value, the inverter active power setpoint is reduced by the fixed PI controller until the voltage comes back under the threshold. This setting only affects the power setpoint of PV inverters.
U1 voltage
Only used when Enable grid voltage control is set to Linear voltage export control. Sets the lower voltage threshold of the linear curve: below U1 voltage, the export power is unrestricted. The U1 voltage must be set lower than the U2 voltage.
U2 voltage
Only used when Enable grid voltage control is set to Linear voltage export control. Sets the upper voltage threshold of the linear curve: at U2 voltage, the export power is reduced to zero. Between U1 voltage and U2 voltage, the export power decreases linearly as the measured grid voltage rises. The U2 voltage must be set higher than the U1 voltage.
The grid voltage measured at the inverter terminals is typically higher than the voltage measured at the grid entrance or grid meter location due to voltage rise along the connection. Therefore, the maximum allowable grid voltage configured in the inverter must be set higher than the maximum grid voltage limit configured in the Embion EMS Controller to prevent unintended inverter disconnection. |
The P1 DSMR 4 protocol does not support phase voltage measurement. Therefore, grid voltage control cannot be used when the grid meter is a P1 DSMR 4 energy meter. |
Off Grid control
![]() |
Your licence has to include PV control or BESS control. Without either, the Off Grid Control settings are not shown in the settings. |
When to use Off Grid Control
Use Off Grid Mode on sites that can operate islanded: a hybrid or battery inverter with a backup/island output, behind a changeover switch or island relay.
Islanded: The site is disconnected from the public grid and operates independently, with the inverter supplying the site’s loads.
Two things have to change as soon as the site islands:
- The inverter, not the Embion EMS controller (EEC), balances the island. The controller stops sending battery setpoints so that the two controllers do not fight each other.
- PV is curtailed statically, not dynamically. Surplus PV cannot be exported while the site is islanded. In Off Grid Mode, the Embion EMS controller stops its normal dynamic active power control and holds PV at one fixed percentage. It shuts PV off completely once the battery reaches the start SoC.
There is no dynamic PV curtailment while off grid. The normal active power control loop, which follows the grid meter and continuously modulates PV, is bypassed. In Off Grid Mode, the EEC uses only two PV output settings: the configured static PV output limit, and 0% once the battery reaches the Start SoC. The EEC does not adjust PV output to follow the load while the site is islanded. Set the static PV output limit so that the island can absorb the available PV power under the expected worst-case conditions. |
The EEC does not perform the disconnection or transfer itself. The changeover gear and the inverter do that. The EEC only reacts to a signal indicating that the site is off grid. |
Before you start
- Inverters, grid settings and active power control need to be configured before starting.
- A potential-free auxiliary contact is available from the changeover switch, island relay or inverter, indicating that the site is off grid.
- IN1 or IN2 is free and not already used by a rule in the GPIO rules wizard. Do not reuse the same input for another function. One input, one function.
- Wire the potential-free contact to IN1 or IN2 on the EEC.
- Before configuring, switch the contact and confirm that the IN1/IN2 status changes accordingly. The input states are reported to the portal, so you can verify the wiring there.
- Note which state the input takes when the site is off grid: High or Low. You will need this when configuring the settings in the HUB Portal.
- For SoC-based PV reduction, a battery (hybrid) inverter is configured. On PV-only sites, the SoC settings have no effect.
Off Grid Control configuration
![]() |
Enable off grid control
Enable to switch the feature on. Disable turns the feature off and prevents you from configuring any other settings.
Input trigger for off grid mode
Select which input the potential-free contact is wired to (IN1 or IN2).
Trigger value
Select the input state that indicates the site is off grid: High or Low. Check the IN1/IN2 status with the site off grid before selecting this value.
Reduce PV in off grid mode
Enable to let the EMS controller limit and shut down PV while off grid.
Static PV output limit %
Sets the maximum PV output while off grid, as a percentage of the rated PV power. Only available when PV reduction is enabled.
Start PV reduction battery SoC
Battery SoC at which PV output is reduced to zero. Only available when PV reduction is enabled. Can be set to 95%, 90% or 85%.
Reset PV reduction battery SoC
How far the SoC must drop below the start value before PV output is restored. Only available when PV reduction is enabled. Can be set to 5%, 10%, 15% or 20%.
Setting up Off Grid Control
Configure and test Off Grid Control in the following order:
- Enable off grid control and select the input connected to the potential-free contact.
- Set Trigger value to the input state that indicates that the site is off grid.
- Enable Reduce PV in off grid mode if the EEC is to limit PV while off grid.
- Set Static PV output limit % to a value that the island can absorb in the worst case: the minimum expected local load plus the maximum battery charge power, rather than the average load. Any excess must be handled by the inverter itself.
- If SoC-based PV reduction is required, set Start PV reduction battery SoC and Reset PV reduction battery SoC. The Start and Reset values form a hysteresis band. For example, with Start 90% and Reset 10%, PV drops to 0% at 90% SoC and returns to the static limit at 80% SoC.
- Save the settings and publish them to the EMS controller.
- With the site on grid, confirm normal operation: the battery follows the active strategy and PV follows the active power control settings.
- Switch the contact to the off-grid state and confirm that the battery setpoint sent by the EEC changes to 0 W and the PV output limit changes to the configured static limit.
- Test the SoC reduction (optional but recommended): temporarily set Start PV reduction battery SoC to a value just below the current battery SoC, save and publish the setting, and confirm that PV drops to 0%. Then restore the intended value and save and publish the setting again.
- Return the contact to the on-grid state and confirm that normal control resumes.
If Reduce PV in off grid mode is disabled, PV is not limited while off grid: the limit is forced to 100%. Only leave this disabled when PV curtailment in the island is fully handled by the inverter itself. |
What the EEC does while off grid
| On grid | Off grid | |
|---|---|---|
| Battery setpoint from the EEC | According to the active strategy | 0 W: the inverter runs the island itself |
| PV output limit | According to active power control | Fixed at the static PV output limit, with no dynamic adjustment (100% when PV reduction is disabled) |
| PV at high battery SoC | Not applicable | 0% from the Start SoC onwards, released back to the static limit once the SoC has fallen by the Reset value. This on/off step is the only SoC-driven PV action; there is no proportional ramp. |
Everything returns to normal control as soon as the trigger input returns to the on-grid state.
Troubleshooting
| Symptom | Likely cause and fix |
|---|---|
| Off Grid Control is missing from the Device settings | The licence has neither PV control nor BESS control. Check the licence. |
| Nothing changes when the contact switches | Trigger value does not match the input state that indicates off grid. Select the other state. Also check the wiring on IN1 / IN2, and that the input is not claimed by a GPIO rule. |
| Off grid mode seems permanently active | Trigger value matches the on-grid state of the contact. Select the state that the input takes when the site is off grid. |
| PV keeps running at full power while off grid | Reduce PV in off grid mode is disabled, which forces the limit to 100%. Enable it and set a static PV output limit. |
| PV never cuts back when the battery is full | SoC-based reduction requires a battery (hybrid) inverter in the configuration, with Reduce PV in off grid mode enabled. On PV-only sites, only the static limit applies. |
| PV does not follow the load in the island | Expected behaviour, not a fault. While off grid, the PV limit is static: dynamic active power control is bypassed. Adjust the Static PV output limit if the fixed value is incorrect for the site. |
| PV switches on and off repeatedly near the start SoC | The reset band is too narrow for the site. Increase Reset PV reduction battery SoC. |
| Changed settings have no effect | The settings have not been saved correctly, or the saved settings have not been published. Check the settings in the HUB Portal and make sure they are published to the EMS controller. |
Cascade
Cascade control lets one Embion EMS controller command other Embion EMS controllers. The commanding controller is the upstream controller. A commanded controller is a downstream controller. A controller can be both at once: a downstream controller can have downstream controllers of its own, so a cascade can be several levels deep.
![]() |
Cascade setup
The upstream controller is a normal installation with its own grid meter and a feature licence that includes battery, PV or load control. Downstream controllers are added on the Cascade page of the upstream controller in the HUB Portal. The page shows how many downstream controllers are configured and how many are online.
Each downstream controller needs the transport licence Cascade Downstream (see the next section) and a grid meter of its own that it reads directly.
The upstream controller must be able to reach every downstream controller via TCP/IP.
A downstream controller works on the setpoints from its upstream controller. It does not run its own plant control from the HUB or the public API. It does still apply its own grid limits, SoC limits and safety functions to the setpoints it receives.
Downstream Licence
A controller becomes a downstream controller by selecting the transport licence Cascade Downstream on the Licence page (Licence, Select Licence, Select transport licence). No other setting is needed. The licence:
![]() |
- starts the Embion interface that the upstream controller uses;
- switches off the controllers own plant control: public API, EPEX plant control, solar forecast plant control and plant control schedules. The upstream controller handles these;
Downstream
On the upstream controller, add each downstream controller in the Cascade section of the Device settings. Give every entry a name. The following parameters configure each downstream controller:
- Serial number downstream controller
- IP address downstream controller
- Maximum battery power of this downstream controller plus everything below it in the cascade kW
- Maximum battery energy of this downstream controller plus everything below it in the cascade kWh
- Maximum SoC for non-solar battery charge — must match the downstream controllers own setting %
- Minimum SoC for battery remote control — must match the downstream controllers own setting %
- Automatic battery charge for this downstream controller and everything below it in the cascade
- Minimum SoC for battery consumption compensation %
- Battery charge priority
- Battery discharge priority
- Maximum PV power of this downstream controller plus everything below it in the cascade kWp
- PV export priority
- Maximum EV power of this downstream controller plus everything below it in the cascade kW
- EV priority
Each maximum is the total for the downstream controller and everything below it in the cascade. A downstream controller that has downstream controllers of its own gets the sum of its own assets and the values it has entered for its own downstream controllers.
![]() |
Serial number downstream controller
The serial number of the downstream controller, used to identify it within the cascade.
IP address downstream controller
The IP address of the downstream controller. The upstream controller connects to it via TCP/IP.
Maximum battery power of this downstream controller plus everything below it in the cascade (kW)
The maximum battery power of the downstream controller is required to determine the active power setpoint and shall equal the sum of the maximum battery power of all underlying controllers. If no battery is connected, this value shall be set to 0.
Maximum battery energy of this downstream controller plus everything below it in the cascade (kWh)
The maximum battery energy of the downstream controller is required to determine the active power setpoint and shall equal the sum of the maximum battery energy of all underlying controllers. If no battery is connected, this value shall be set to 0.
Maximum SoC for non-solar battery charge — must match the downstream controllers own setting (%)
Specify the maximum SoC for all charging actions, except when charging with negative grid power. This value must be equal to or lower than the configured Maximum SoC. The difference can only be charged if Charge with Negative Grid Power is enabled and the grid power is negative. The value should match the settings of the downstream controller(s).
Minimum SoC for battery remote control — must match the downstream controllers own setting (%)
Specify the minimum state of charge (SoC) to which the battery can be discharged via remote control. This value must be equal to or higher than the configured Minimum SoC. The difference is used solely to compensate for the grid import limit using the battery.
When generation control is set to maximum via the public API or HUB, the battery will discharge until this SoC is reached. However, when the battery discharges due to remotely set grid limits (via public API or HUB), the discharge is not restricted by this value.
The value should match the settings of the downstream controller(s).
Automatic battery charge for this downstream controller and everything below it in the cascade
When this setting is enabled, the batteries of the downstream controller(s) will receive a charge setpoint as soon as the priority allows. When disabled, this upstream Embion EMS Controller will not automatically charge the batteries, except when consumption is set to maximum or Charge Battery with Grid Return Power is enabled.
If this function is used in combination with own consumption compensation, the Maximum SoC for Non-Solar Charge must be at least 2% lower than the Minimum SoC for Consumption Compensation.
Minimum SoC for battery consumption compensation (%)
Specify the minimum SoC to which the batteries of the downstream controller(s) can be discharged during own consumption compensation. (This function must be enabled in the Active Power Control settings.)
Battery charge priority
Set the charge priority of the batteries of the downstream controller(s). When the priority is available and the batteries are allowed to charge, a charge setpoint is issued to the batteries. The charge priority should be lower (represented by a higher number) than the discharge priority.
Battery discharge priority
Set the discharge priority of the batteries of the downstream controller(s). When the priority is not yet available, the batteries will discharge at maximum power. This allows the discharge to be used for peak shaving to prevent exceeding grid limits. The discharge priority should be higher (lower number) than the charge priority.
**Maximum PV power of this downstream controller plus everything below it in the cascade (kWp **
The peak power of all PV panels connected to the downstream controller and everything below it, in kWp. Enter 0 if there is no PV.
PV export priority
1 is the highest priority, 10 the lowest. When export must be reduced, PV with a low priority (high number) is reduced first and PV with priority 1 last.
Maximum EV power of this downstream controller plus everything below it in the cascade (kW)
The sum of the maximum charge power of all EV chargers on the downstream controller and everything below it. Enter 0 if there are no EV chargers.
EV priority
The priority of the EV chargers of the downstream controller(s) power can be configured. When power is available for consumption, the Embion EMS Controller increases loads according to their priority, with higher-priority loads (lower numbers) being released first and reduced last.
RTI (Realtime Interface)
RTI is used to receive limits from the grid operator.
RTI hardware setup
When using RTI, two extra devices are required:
- Embion EMS RTI Endpoint
- Endpoint grid operator
Contact your grid operator to obtain the Endpoint grid operator.
Connect the ETH1 port of the Embion EMS Controller to the X2 port of the Embion EMS RTI Endpoint using the provided, green cable. The ETH0 port of the Embion EMS Controller can be used regularly.
The X1 port of the Embion EMS RTI Endpoint should be connected to the Endpoint grid operator. Use a standard Ethernet cable directly between the two ports. It is not possible to use a (local) network between the Embion EMS RTI Endpoint and the Endpoint grid operator.
RTI configuration setup
To enable RTI, enable control of the grid operator in the Device settings.
![]() |
Modbus
This explains the Modbus setup for:
- TCP
- RTU-A (X10)
- RTU-B (X11)
- RTU-C (X12)
![]() |
Setup TCP
![]() |
TCP Client / Server
To enable / disable Modbus TCP server on the Embion EMS Controller TCP, select the desired setting:
- Client (default)
- Client & Server
The Modbus client is used to communicate with the configured assets, while the Modbus TCP server allows external controllers with Modbus client support to read data from or control the Embion EMS Controller; please contact your sales representative for the current Modbus register layout.
TCP Server interface
Select to desired Modbus interface. For now, only one (Version 1) interface is available.
TCP Server IP port
Enter the TCP port for the Modbus TCP server connection, which is used to host the Modbus server on the IP address of the Embion EMS Controller; it is recommended to use port 502 (this is the default).
TCP Server Modbus Unit ID
Enter the Modbus unit ID for the Modbus TCP server connection, which is used to identify the Embion EMS Controller on the Modbus network; the valid range is 1–247, as defined by the Modbus protocol.
RTU configuration
The following inputs are required to complete RTU configuration:
-
RTU Client / Server
-
RTU Baudrate
-
RTU Parity
-
RTU
-
RTU Stopbits
This is true for each of the RTU ports: A, B and C
![]() |
RTU Client / Server
Similar to the TCP Client / Server setting, only difference is that the Server setting is not available yet on Modbus RTU.
RTU Baudrate
Select the baudrate for the RTU connector, options are:
- 9600 (default)
- 19200
- 38400
- 57600
- 115200
- 230400
RTU Parity
Select the parity for the RTU connector, options are:
- None (default)
- Even
- Odd
RTU Databits
Select the databits for the RTU connector, options are:
- 8 bits
- 7 bits
RTU Stopbits
Select the stopbits for the RTU connector, options are:
- 1 bit
- 2 bits
Updates
![]() |
Update Strategy
![]() |
Select the strategy to run updates. Two options are available:
- Automatic: Embion EMS Controller will automatically download and install available updates at night.
- Manual: If enabled a notification is shown when an update is available. The device will not automatically install updates.
Channel
Select the active update channel.
- Latest: Receive the latest official releases, this is the default setting.
- Stable: Receive only stable updates (versions that have been tested in a production environment for at least several weeks).
- Beta: Receive beta versions (non-official releases).
The Beta channel is not recommended for devices in a production environment, as releases in this channel are still in the testing phase and no warranty is provided for the software’s functionality. |
![]() |
Network
![]() |
Network Priority
Set the priority of the network interfaces. The EEC uses the highest-priority interface first. If it cannot reach the internet through that interface, it automatically switches to the next interface in the priority list.
![]() |
For setting up network priority, the following inputs are required to complete the configuration:
Custom priority
If set to Disable the configuration will use the default priorities: ETH0, ETH1, Wi-Fi, USB. If you want to divert from these defaults choose Enable.
1st choice, 2nd choice, 3rd choice, 4th choice
For each of these choose one of ETH0, ETH1, Wi-Fi, or USB.. The network will prioritise these interfaces from highest (1st choice) to lowest (4th choice).
Network ETH0 and ETH1 setup
For setting up either the ETH0 or ETH1 ports, the following inputs are required to complete the configuration:
- Static / DHCP (For ETH1 this setting has one additional option: "Bridge with ETH0")
- ETH IP address
- ETH Netmask
- ETH Gateway address
- ETH DNS
![]() |
Static / DHCP / Bridge
Select the type of ETH0 or ETH1 connection, options are:
- DHCP
- Static
For ETH1 this setting can be set to "Bridge with ETH0". This will bridge the ETH0 and ETH1 to one port, forwarding all network traffic through. Network settings of ETH0 will remain used by the controller. All data received / send over ETH0 & ETH1 is forwarded to the other ETH port.
ETH IP address
Enter the IP address of the ETH network, for example: “192.168.0.10”.
ETH Netmask
Enter the ETH0 or ETH1 netmask, for example, “255.255.255.0”.
ETH Gateway address
Enter the IP address of the network default gateway, for example, “192.168.0.1”. This field can be left empty if there is no default gateway for this connection, meaning the port will not provide internet access.
ETH DNS
Enter the DNS setting for ETH0 or ETH1, for example, “8.8.8.8”. This field can be left empty if no DNS is required.
Network Wi-Fi settings
For setting up the Wi-Fi network, the following inputs are required to complete the configuration:
- Enable Wi-Fi
- Available Wi-Fi networks
- Network password
- Static / DHCP
- Wi-Fi IP address
- Wi-Fi Netmask
- Wi-Fi Gateway address
- Wi-Fi DNS
![]() |
Enable Wi-Fi
Enable or disable Wi-Fi
Available Wi-Fi networks
Select a Wi-Fi network from the list of available networks. The connection strength (in %) is shown next to each network name, and the list is sorted from the strongest connection at the top to the weakest at the bottom.
Network password
Enter the Network password for the selected Wi-Fi network.
Static / DHCP
Select the type of Wi-Fi connection, options are:
- DHCP
- Static
Wi-Fi IP address
Enter the IP address of the Wi-Fi network, for example: “192.168.0.10”.
Wi-Fi Netmask
Enter the Wi-Fi netmask, for example, “255.255.255.0”.
Wi-Fi Gateway address
Enter the IP address of the Wi-Fi default gateway, for example, “192.168.0.1”. This field can be left empty if there is no default gateway for this connection, meaning this connection will not provide internet access.
Wi-Fi DNS
Enter the DNS setting for the Wi-Fi network, for example, “8.8.8.8”. This field can be left empty if no DNS is required.
The Embion EMS controller only supports the WPA2 security standard. |
For optimal performance, it is recommended to use an Ethernet connection instead of Wi-Fi, as Wi-Fi quality depends on the network and may lead to stability and performance issues. |
System
This section with system settings contains the following items:
- Display setup (brightness and contrast settings)
- Language selection
- Timezone
- Upload interval
Display setup
Here you can select the low level of the backlight intensity. The Embion EMS Controller will dim the backlight to this level when the buttons have not been pressed for a while. Make your selection from the following options:
- Off
- Low
- Medium
- High
- On
![]() |
Language Selection
Configures the system language for the Embion EMS controller, changing this setting will change the language used on the Embion EMS controller Display. Change the language for the HUB Portal by clicking your profile icon on the top-right and selecting "My Account".
![]() |
Timezone selection
Sets the local timezone used by the Embion EMS Controller.
![]() |
Upload interval
The upload interval for asset data from the EMS to the HUB can be set to 1 (default), 5, or 15 minutes. Longer intervals can help reduce data usage in situations with limits, such as when using a 4G modem. Note that data uploaded at a 5- or 15-minute interval cannot be restored to a shorter interval later.
![]() |
Dashboards
Dashboards can be reached by clicking the dashboard symbol on the left side menu or on the button on the homepage.
![]() |
In this section, multiple custom dashboards can be created to display an overview of the plant data. Different widgets are available, which can be customised to best suit this plant.
Dashboard example
This is an example of a configured dashboard. Users are able to configure and arrange the widgets according to their preferences.
![]() |
Add dashboard
By default, there is a dashboard called “My dashboard” that gets added when an EMS Site (Namespace) is created or when the last dashboard in an EMS Site is deleted. This dashboard contains some standard plant widgets. The created dashboard can be removed, and new dashboards can be added.
By going to the Options section in the upper right corner and pressing the “Create” button, users can add a new dashboard to their EMS Site. Users can set a name, icon, and colour to differentiate between dashboards. When creating a dashboard, it is possible to select a dashboard template to set it up easily.
Alternatively you can use the option "Update" to edit the handle of the current dashboard or "Remove" to delete the current dashboard.
![]() |
Select dashboard
By clicking on the button that displays the current dashboard name, users can access a list of all available dashboards. This action opens a view where users can see a list of the available dashboards. From this list, users can select a different dashboard by choosing the desired option. This feature allows users to easily switch between different dashboards and navigate to the one they want to view or interact with.
![]() |
Widgets
The dashboard section provides a variety of widgets users can utilise to enhance their dashboards and visualise data effectively. Currently, there are multiple widgets available, organised into three different categories. The widgets selection can be toggled by pressing the “Widgets” button in the top right.
Basic widgets:
- Plant overview
- Plant chart
- Plant consumption
- Inverter overview
- Inverter group
- Inverter groups
- Meter overview
- EV charger overview
- CO₂ reduction
- Solar forecast
Pricing widgets:
- EPEX chart
- Actual EPEX price
Advanced widgets:
- Bar chart
- Line chart
- Last value
- Gauge meter
Widget status LED
Several overview widgets use status LEDs to show the data’s status to users. These LEDs visually indicate whether the data is live, out of sync, or unavailable. Users can get more details, such as data timestamps or error/warning messages, by hovering over these status LEDs. For example user can indicate the status of their plant, inverter (addresses) or meter.
Green:
- Live data
- The widget is currently displaying real-time data. All data streams are active and up-to-date.
Orange:
- Data out of sync
- Data has been uploaded today, but it is not being updated in real-time so the widget won’t display any data.
Red:
- No data available
- No data has been uploaded today, and the widget won’t display any data.
Status example
In the example below, an inverter group widget displays a warning status LED. When hovering over the status LED, a message saying “address warning” is shown. Address statuses can be viewed by setting the widget configuration to expert mode.
![]() |
In the example below, the individual statuses for each address are displayed. This allows the user to identify which address is causing the warning within the inverter group widget.
![]() |
Basic widgets
Basic widgets provide users with the ability to add widgets to their dashboard with minimal configuration steps.
Plant overview
The plant overview widget show users the basic information about their selected plant. The sun power, grid power and total consumed plant power is shown in an easy to read widget. The flow lines will move in the direction where the active power is going.
![]() |
Negative values indicate that electricity is sent back to the grid or inverter. |
Configuration
To configure the plant overview widget, users only have to select their Embion EMS Controller device from the list. It is also possible to add a preferred icon to the widget that is shown by plant power.
Plant chart
![]() |
Chart data
The plant chart widget can provide the following data in an area chart:
Solar power
- The generated solar power over time Grid power
- The power sourced from the grid (positive) or returned to the grid (negative) over time Plant power
- The power consumed within the plant (solar power - grid power) over time Plant power direct sun
- The plant power directly sourced from sun power Plant power direct grid
- The plant power directly sourced from grid Relative plant solar
- The relative (0-100%) plant power which is directly sourced from sun Relative plant grid
- The relative (0-100%) plant power which is directly sourced from grid Actual reduction
- The actual (relative) inverter power limit (100% is no limit, 0% is fully limited). Battery power
- The actual battery power. State of charge
- The state of charge of total battery capacity in the plant. EV charger power
- The actual EV charger power.
The plant data can’t become negative at the moment. When the plant returns energy, the plant power is limited at 0W. |
Yield and consumption
Yields can be displayed above the chart for the selected range. When switching to a larger range than ‘day,’ such as ‘month,’ the chart will show yields and consumption instead of the selected plant data.
![]() |
Configuration
To configure the plant chart widget, users have to select their Embion EMS Controller and select which data is shown in the chart. Also it’s possible to enable yield to be displayed above the chart. The data can be shown five-minutely or quarter-hourly by changing the period.
Plant Consumption
![]() |
The plant consumption widget displays the following data inside a pie chart:
Relative plant power from solar
- The relative (0-100%) plant power which is directly sourced from sun Relative plant power from grid
- The relative (0-100%) plant power which is directly sourced from grid
The values shown in the plant consumption pie are determined from actual measured powers and therefore only represent the relative actual power consumption. |
Configuration
To configure the plant consumption widget, users have to select their Embion EMS controller.
Meter overview
![]() | ![]() |
The meter overview widget provides the following data based on the selected data type:
Selectable data types
Basic
- Active power
- Imported energy
- Exported energy
- Used grid energy (if split solar/grid is enabled for the load meter)
- Used solar energy (if split solar/grid is enabled for the load meter)
Expert
- All the basic data which is available
- Phases (one or three phases based on the meter used)
- Reactive power (not available for all energy meters)
- Apparent power (not available for all energy meters)
Configuration
To configure the meter overview widget, users have to select their Embion EMS controller and energy meter of which the data should be shown. The user is able to select basic or expert mode for the data that needs to be shown.
The user is able to configure the time range from which the energy values are shown. E.g. setting the time range to hour will only show the imported, exported, solar and grid energy for the consumed or delivered in the last hour.
Inverter overview
![]() | ![]() |
The inverter overview widget provides the following data based on the selected data:
Selectable data types
Basic
- Active power
- Daily yield
- Inverter image based on selected inverter (More inverter images will be added later)
Expert
- All the basic data which is available
- Phases (one or three phases based on the inverter that is used)
- Inner temperature of the inverter
Configuration
To configure the inverter overview widget, users have to select their Embion EMS controller and inverter of which the data should be shown. The user is able to select basic or expert mode for the data that needs to be shown.
Inverter group
![]() | ![]() |
Selectable data
Basic
- Total active power of the inverter group
- Total daily yield of the inverter group
Expert
- All the basic data which is available
- Active power and daily yield for each address in the inverter group
Addresses that have uploaded data in the last 7 days will be shown in the widget. If an address has no data from the past 7 days, it will be removed from the address list.
Configuration
To configure the inverter group widget, users only have to select their group of inverters which the data should be shown. The user is able to select basic or expert mode for the data that needs to be shown.
Inverter groups
![]() | ![]() |
Selectable data
Basic
- Total active power of all the inverter groups in the selected plant
- Total daily yield of all the inverter groups in the selected plant
Expert
- Total active power and daily yield of each inverter group
- Active power and daily yield for each address in the inverter group
Addresses that have uploaded data in the last 7 days will be shown in the widget. If an address has no data from the past 7 days, it will be removed from the address list.
Configuration
To configure the inverter groups widget, users only have to select their plant of which the data should be shown. The user is able to select basic or expert mode for the data that needs to be shown.
EV Charger overview
![]() | ![]() |
The EV charger overview widget provides the following data based on the selected data:
Selectable data
Basic
- Charge power
- Total energy
Expert
- All the basic data which is available
- Phases (one or three phases based on the meter used)
Configuration
To configure the EV charger overview widget, users have to select their Embion EMS controller and charger of which the data should be shown. The user is able to select basic or expert mode for the data that needs to be shown.
The user is able to configure the time range from which the energy values are shown. E.g. setting the time range to hour will only show the total energy for the consumed or delivered in the last hour.
CO₂ reduction
The CO₂ reduction widget shows the total carbon dioxide emissions, in kilograms, saved by a specific plant. The data can be viewed by year, month or day. Hovering over a section of the graph provides more detailed information.
In the widget settings, you can also enable reference values to make the information easier to interpret. For example, you can display how many trees would need to be planted to achieve the same amount of CO₂ reduction.
![]() | ![]() |
Solar Forecast
The Solar Forecast widget shows the predicted solar power generation for a selected period: yesterday, today or tomorrow. The graph can also display the actual solar power generated up to the current moment, making it easy to compare the forecast with the measured output.
In the widget settings, you can choose from three graph styles: line chart, area chart or bar chart.
![]() |
Pricing widgets
Pricing widgets provide users with the ability to add widgets to their dashboard which give insight to their energy price based on EPEX.
EPEX chart
The EPEX chart widget is used to display graphs of the EPEX price in hours. It is possible to get insight in the prices of next day when they are available, mostly around 1:00 pm. To improve clarity, the chart uses distinct colours for negative and positive values. Both colours are included in the legend for easy reference.
![]() |
Configuration
To configure the EPEX chart widget, the only input that is needed are the bidding zones needed to be shown. It is possible to add up to four different bidding zones in one chart. It is possible to show the data in a line, area or bar chart.
Actual EPEX price
![]() | ![]() |
The actual EPEX price widget is used to display the actual or daily EPEX price based on the selected data.
Selectable data
- Actual price: displays the actual live EPEX price for the current time and date.
Daily period
- Average: displays today’s average EPEX price.
- Minimum: displays today’s minimum EPEX price.
- Maximum: displays today’s maximum EPEX price.
Possible units
- kWh: displays the EPEX price in EUR/kWh.
- MWh: displays the EPEX price in EUR/MWh.
Configuration
To configure the actual EPEX price widget, users are able to choose which value and unit should be shown in the widget.
Advanced widgets
Advanced widgets provide users with the ability to add widgets to their dashboard with certain configuration possibilities. Users are more free to configure a chart based on preferred data of their plant.
Bar chart
The bar chart widget allows users to present data using vertical bars, making it easy to visually compare different categories or values. This widget is ideal for displaying categorical or discrete data and highlighting comparisons or distributions.
![]() |
Configuration
To configure the bar chart widget, users can select up to 10 data series. They can also select a period, range and value type (minimum, maximum, difference or average).
When more than four data series are selected, only the daily, weekly and monthly periods are available. The graph range is then automatically set to the corresponding period. |
Line chart
This line chart widget enables users to create interactive line charts that display trends, patterns, and variations over time. It is a powerful tool for visualising data with continuous variables and analysing data trends.
![]() |
Configuration
To configure the line chart widget, users are able to display up to 4 data series as line or area chart. It is also possible to select a period, range and type of values (min, max, difference and average).
Last value
The last value widget provides a quick and concise representation of the most recent value or data point.
![]() | ![]() |
Configuration
To configure the last value widget, users need to select a data series. It is also possible to select a period (last value, hourly, daily). When the selected period is not last value, a type of value (min, max, difference and average) can be set.
Gauge meter
The gauge meter widget provides a quick and concise representation of the most recent value or data point.
The minimal and maximum value of the gauge meter is based on data of the last 30 days. |
![]() | ![]() |
Configuration
To configure the gauge meter, users can select a plant, meter or inverter (group) data series which needs to be shown.
Add widget
Users can add widgets to their dashboard by utilising a simple drag-and-drop functionality from the widget list. Once a widget is dragged and dropped onto the dashboard, it will appear ready to be configured according to the user’s requirements.
![]() |
Arrange widgets
Users have the ability to arrange multiple widgets on the dashboard according to their preferences. This can be done by dragging the widgets using the top bar of the header and repositioning them within the dashboard. By simply clicking and holding the top bar of a widget, users can move it to a new location on the dashboard.
In addition to rearranging the widgets, users can also resize them to fit their desired dimensions. This can be achieved by selecting a widget and dragging the corner of the widget to adjust its size. By dragging the corner handle, users can increase or decrease the width and height of the widget, allowing for precise customisation and optimal use of available space.
![]() |
Configure widgets
Users can easily configure their widgets by accessing the settings options available within each widget. To access the settings, users simply need to click on the settings icon located within the widget itself. By clicking on this icon, users can access a panel where they can adjust various settings specific to that particular widget.
Additionally, users have the ability to change the name of a widget by directly clicking on its existing name. Clicking on the widget name activates an editing mode, allowing users to modify the name as desired. This feature enables users to provide descriptive and meaningful names to their widgets, making it easier to identify and understand the purpose or content of each widget within the dashboard.
![]() |
Configure form example
![]() |
Devices
To select the data of a specific device for display in a graph, users have the option to choose up to four data lines to represent different variables or metrics. Users can search in all the possible devices and variables to access them easy.
The UIDs are arranged as follows: [device name] / [group identifier]_[group name]:[device address]:[string id] Where the string id is only applicable for solar inverter.
![]() |
![]() |
Period
Select a period or interval for the widgets to be shown. Selecting Hourly will show one datapoint for each hour.
![]() | ![]() |
Value type
Select the value type that is needed to be shown in the widget.
![]() |
Maximum returns the maximum measured value in the selected period
Minimum returns the minimum measured value in the selected period
Average returns the average of all values in the selected period
Difference returns the difference between the first and last sample in the selected period
Range
Select the time range for the widget. Depending on the selected period, not all range options are available.
![]() |
Maximum returns the maximum measured value in the selected period
Minimum returns the minimum measured value in the selected period
Average returns the average of all values in the selected period
Difference returns the difference between the first and last sample in the selected period
Unit
Select the unit for values within the widget.
![]() |
Icon
Select an icon for the widget, this icon is shown in the back of the widget.
Graphs
Navigate graphs
Users have the convenience of navigating through their graph widgets using the arrow buttons provided. These arrow buttons allow users to move forward or backward in time, enabling them to explore different time periods or intervals within the graph data.
In addition to the arrow buttons, there is an agenda button available. Clicking on the agenda button will automatically set the graph widget back to the current date, providing users with an easy way to quickly return to the most up-to-date data and view.
![]() |
Export graphs
Users have the option to export graph widgets by utilising the download button located in the bottom left corner of the widget. Clicking on this will open a set of options, including the ability to export the graph widget as a JPEG image or a PDF document.
![]() |
Disable graphs
Users have the ability to disable one or multiple data lines in a graph by simply clicking on their corresponding names in the legend.
![]() |
Energy pricing
The Energy Pricing section can be reached by clicking the symbol on the left side menu or on the buttons on the homepage.
In this section, users can enter energy pricing information for each device. This enables them to control their devices based on the current energy price using control rules (if plant control is enabled). It is also possible to use data from solar forecasts to optimise the automated control.
![]() |
Pricing schemes
On the Pricing Schemes page, users can fill out energy pricing information by creating a pricing scheme, allowing them to be used in multiple devices in the EMS Site (Namespace). A list of pricing schemes will be displayed with their selected bidding zone and provider margin.
![]() |
Add or edit pricing schemes
It is not recommended to edit pricing schemes that are already being used in other devices, as any changes made will also affect them. For historical accuracy, it is generally a good practice to create a new pricing scheme when changes in your energy contract were made, instead of editing an existing pricing scheme. |
To configure a pricing scheme, the following parameters are required:
Name: this name will be displayed when selecting pricing schemes on devices.
Colour: is optional for recognisability when configuring multiple schemes.
Variant: the variant of the pricing scheme (see Pricing scheme variants below).
Pricing scheme variants
At the moment, only the Day-ahead electricity price pricing scheme variant is available. This variant makes use of electricity day-ahead auction data fetched from the ENTSO-E Transparency Platform.
The Day-ahead electricity price pricing scheme variant requires the following additional parameters:
Bidding zone: bidding zone of the country/countries users want to use.
Resolution: the granularity of the day-ahead electricity market data that your energy provider may use (either 60, 30 or 15 minutes).
Energy provider margin: an extra margin in €/kWh induced by your energy provider (if applicable).
In addition to the parameters above, the disclaimer must be accepted when creating a pricing scheme.
![]() | ![]() |
Device control
On the Device control page, users can configure their devices with pricing schemes and define control rules. A list of devices in the users EMS Site (Namespace) is shown with their current active scheme and amount of control rules.
![]() |
Device control
In the device settings menu, users can configure energy pricing related features for their device. This menu allows users to assign pricing schemes to the device and setup automatic plant control via control rules (if supported and enabled for the device).
It is also possible to access the control rule simulator by pressing the Simulate button, which uses (historical) day-ahead auction data to simulate which plant control commands are sent to a device at a specific point in time.
![]() | ![]() |
Add or edit pricing schemes
To assign a pricing scheme to the selected device, the following inputs are required:
Pricing scheme: the pricing scheme that will be assigned to the device.
Start date: start date of when pricing scheme needs to be used.
End date: end date of the pricing scheme (can be left empty, meaning it will indefinitely stay active).
![]() | ![]() |
Solar Forecast
This section is used to provide information about the location and configuration of the solar panels used by this plant. Combined with the solar forecast, this data can be used to set up control rules and maximise the plant’s energy usage.
![]() | ![]() |
Location
![]() |
The location is selected by entering the plant’s address. This is necessary to provide an accurate forecast for that specific area.
Inverters & Panels
![]() |
To add an inverter, select one from the drop-down list of inverters connected to the plant. Give the inverter a descriptive name for reference, enter its AC capacity (kW), and then select the associated inverter group address or addresses.
For each inverter, at least one solar panel group must be added. Each panel group requires a descriptive name, the DC capacity (kW), the tilt angle, and the azimuth angle.
The tilt indicates the angle, in degrees, at which the solar panels are installed relative to the horizontal. The azimuth indicates the compass direction, in degrees, that the panels are facing. For example, an azimuth of 180° means the panels face south, while 90° and 270° indicate east- and west-facing panels respectively.
Control rules
Plant control needs to be enabled on the device in order to control it via control rules. The device must also have an active pricing scheme. |
Devices that have plant control enabled and have an active pricing scheme assigned can automatically be controlled based on energy price, solar forecast and/or time using control rules. These control rules allow you to minimise power generation and maximise power consumption when the energy price becomes negative for example.
The order of the control rules on the device page matter, as only the first occurrence of a command will be sent to the device. If the current control rule doesn’t contain a given command, but a rule below does, then that command is also sent to the device. The priority flows from the top to the bottom of the list, with the rule at the top having the highest priority.
You can change the order of the control rules by dragging them (desktop only) or by clicking the up or down arrow on the left side control rule (next to the control rule number).
Add or edit control rules
Control rules are divided into various ‘blocks’, which can be enabled or disabled depending on the requirements of the control rule.
All enabled blocks must become true in order for a control rule to activate, so if you have both an If and a Between block, the conditions in the If block must be valid, and the current time must be included in the Between block.
Control rules must meet the following requirements:
- Have either an active If, Between or When block (or a combination of these).
- Have at least one command with an explicit value in the Then block.
In addition to the various blocks, an optional colour can be selected in order to make it visually distinct from other control rules in the list.
![]() | ![]() |
If block
![]() |
In the If block, users can create one or more (up to a maximum of 5) conditions that must become true in order for the control rule to activate.
This block can be used to check whether the energy price or daily energy price difference is higher or lower than a given value for example.
One condition will be shown by default. Additional conditions can be created by pressing the Add extra condition button. If you wish to remove a condition, you can press the corresponding Remove button (only present if multiple conditions are present).
If multiple conditions are defined, the following parameter is defined:
Validation strategy: defines the manner in which the underlying conditions have to be true before the control rule activates.
- All of these conditions must be true: All conditions must be true before the control rule could activate.
- At least one of these conditions must be true: One or more conditions must be true before the control rule could activate.
The following parameters are required for each condition:
Property: the property to check for.
- Energy price excl. tax: The actual energy price (excluding taxes).
- Daily energy price difference: The difference between the highest and lowest energy price of the day.
- Solar forecast next 4h
- Solar forecast next 8h
- Solar forecast rest of day
- Solar forecast of today
- Solar forecast of tomorrow
Operator: the operator that is used to evaluate the condition (greater than, less than, equals to, etc.).
Value: the value that the property will be evaluated against.
An example:
If you want the control rule to activate when the energy price becomes or is lower than €0.00 and the daily energy price difference is above €0.10, the parameters will have to be set to the following values:
Validation strategy: All of these conditions must be true
Condition 1:
Property: Energy price excl. tax
Operator: Under or equals to
Value: 0
Condition 2:
Property: Daily energy price difference
Operator: Above
Value: 0.10
Equals to: Is true when both values are equal. Above: Is true when value A is higher than value B. Above or equals to: Is true when value A is either higher than or equal to value B. Under: Is true when value A is lower than value B. Under or equals to: Is true when value A is either lower than or equal to value B. Not equals to: Is true when value A is not the same as value B. |
When block
![]() |
The When block allows users to trigger certain control rule commands on moments when the energy price is at their highest or lowest in between the given time period, which can be used to limit consumption on the four hours that the energy price is at their highest for example.
It is also possible to fetch the x lowest or highest consecutive entries, which will look for the lowest or highest average spanning the specified length.
The following parameters are required:
Property: The property to check for.
Property operator: Specifies whether the entry should occur in the x lowest/highest entries.
- is: The entry occurs in the x lowest/highest entries
- is not: The entry doesn’t occur in the x lowest/highest entries.
Entries: The amount of lowest/highest entries that the control rule should validate for.
Entry operator: Specifies which entries to fetch
- Lowest: Fetches the entries where the property value is at its lowest.
- Highest: Fetches the entries where the property value is at its highest.
- Lowest consecutive: Fetches the moment where the average of the x consecutive entries is at its lowest.
- Highest consecutive: Fetches the moment where the average of the x consecutive entries is at its highest.
Unit: The unit (duration) of a single entry (quarter hours, half hours or hours).
Time period: Specifies from which time window the entries are evaluated. Of the day: Checks all entries of the current day (0:00 - 23:59). In between: Checks the entries specified in the Between block.
An example:
If you want to charge an EV that requires 2 consecutive hours to charge when the energy price is at its lowest point of the day, the parameters will have to be set to the following:
Property: Energy price excluding tax
Property operator: Is
Entries: 2
Entry operator: Lowest consecutive
Unit: Hours
Time period: Of the day
For block
This block only works in conjunction with the If and/or When block. |
![]() |
The For block can be used to check if the condition in the If block is true for an x amount of consecutive entries, which can be used to ensure that the condition is true for the duration that longer tasks may have or to prevent the rule from activating if the condition is matched for too long (i.e. for subsidies).
If the When block is enabled. The For block checks if the condition in the When block is true for an x amount of consecutive entries, so if the When block is set to check for the lowest 4 entries, the For block validates if the x consecutive entries occur in the lowest 4 entries.
The following parameters are required:
Operator: the operator that is used to evaluate the condition (greater than, less than, equals to, etc.).
Entries: the amount of consecutive entries that will be evaluated against
Unit: the unit (duration) of a single entry (consecutive quarter hours, half hours or hours)
An example:
If you want the control rule to activate when the If block condition was met for at least two consecutive hours, the parameters will have to be set to the following values:
Operator: Above or equals to
Entries: 2
Unit: Consecutive hours
Between block
The Between block currently uses the Amsterdam time zone (CET / CEST) to evaluate the given time constraints. |
![]() | ![]() |
The Between block can be used to specify when a control rule may activate, which can be used so that some control rules may only validate outside working hours or only on weekends.
The Between block can be fully stand-alone, activating the control rule between the given time constraints, or to work in conjunction with other blocks (to only activate a rule when the energy price is low on weekdays for example).
The following parameters are required:
Begin time: Time from when the control rule may activate (24 hour format)
End time: Time from when the control rule will stop activating (24 hour format)
Days: The days of the week that the control rule can activate (works in conjunction with the time constraints) (click to select / deselect)
Activate on all months: If enabled, the control rule can activate in all months of the year. If disabled, you can select the months in which the control rule may activate (click to select / deselect). Configuration of months is only possible on Embion EMS.
If both the begin time and end time are set to 00:00, the rule will stay active throughout all enabled days, so if all days are enabled the rule will indefinitely stay active.
An example:
If you want the control rule to activate on weekdays between 9:00 and 17:00 in all months of the year, the parameters will have to be set to the following values:
Start time (hours and minutes): 9 : 00
End time (hours and minutes): 17 : 00
Days: monday, tuesday, wednesday, thursday, friday
Activate on all months: Enabled
Then block
![]() | ![]() |
In the Then block, you can define the commands that will be sent to the device once the control rule activates. It is possible to send multiple commands at once.
The Then block has 2 different modes:
Basic: In the basic mode, you can choose a predefined action to execute. If you switch to the expert mode, you can view the underlying commands that are sent to the device.
Expert: In the expert mode, you are able to adjust all commands that can be sent to the device. The expert mode is further explained below.
Commands can either be enabled or disabled. When a command is disabled, it will make the command available for changes by a control rule with a lower priority, but at least one command is required for the control rule to be effective.
The order of the control rules on the device page matter, as only the first occurrence of a command will be sent to the device. If the current control rule doesn’t contain a given command, but a rule below does, then that command is also sent to the device.
Commands
Not all commands are available for every device. The available commands depend on the software version and the type of controller. |
The following commands can be assigned:
| Controller | Min. software version | Command | Description |
|---|---|---|---|
| - | - | Control generation | Affects power generation of the plant (see further explanation below) |
| - | - | Control consumption | Affects power consumption of the plant (see further explanation below) |
| - | - | Active power import limit (W) | Limit in Watts for importing power |
| - | - | Active power export limit (W) | Limit in Watts for exporting power |
| Embion EMS | 4.2.0 | Relative power import limit (%) | Limit in percentage for importing power |
| Embion EMS | 4.2.0 | Relative power export limit (%) | Limit in percentage for exporting power |
| Embion EMS | 4.2.0 | Control PV limit (%) | Limit in percentage for power generation of solar inverters |
| Embion EMS | 4.2.0 | Control EV limit (%) | Limit in percentage for power consumption of EV chargers |
| Embion EMS | 4.2.0 | Control battery setpoint (W) | Setpoint in Watts for charging (positive value) or discharging (negative value) of the Battery Energy Storage System (BESS) |
| Embion EMS | 5.2.0 | Minimum BESS state of charge (%) | Minimum state of charge in percentage for the Battery Energy Storage System (BESS) |
| Embion EMS | 5.2.0 | Maximum BESS state of charge (%) | Maximum state of charge in percentage for the Battery Energy Storage System (BESS) |
| Embion EMS | 5.2.0 | Desired BESS state of charge (%) | Desired state of charge in percentage for the Battery Energy Storage System (BESS) |
Further explanation of control generation and consumption commands
- The control_generation and control_consumption commands can be used to control plant generation and consumption independently of the plant configuration.
- Setting control_generation to min reduces the power generation to the minimum, resulting in solar power converters to shutdown and wind turbines to stop.
- Setting control_generation to nom allows generation of solar and wind to operate normally.
- Setting control_generation to max allows the start of any extra generators (if available at the plant) or to start discharging available batteries.
- Setting control_consumption to min reduces the controllable loads like heat pumps and EV-chargers to minimum consumption.
- Setting control_consumption to nom enables normal controllable loads to operate within the plant limits.
- Setting control_consumption to max increases the power for controllable loads to maximum. EV-chargers will increase charging power to maximum (within plant limits) and heat pumps will increase or decrease their setpoint to increase power consumption. Connected battery systems will be allowed to charge within battery and plant limits.
Plant control actions sent via the public API will block any actions generated by automatic plant control until they expire. |
Control rule simulator
The control rule simulator can be used to simulate which plant control commands are sent to the device using (historical) day-ahead auction data.
If no day-ahead auction data is available, a warning will be shown. It is advised to check if a specific point in time has day-ahead auction data using the day-ahead price chart widget in the Dashboard app.
![]() |
Notification Triggers
The Notification Triggers section allows users to view and create automated notifications based on device data conditions. Users can configure triggers that monitor specific device values and send notifications when certain thresholds or conditions are met.
Notification triggers are useful for:
- Alerting when inverters report a warning or error state.
- Notifying when a connected battery (BESS) is fully charged or nearly empty.
- Notifying when inverters are reduced to limit power generation.
- Alerting if power limits were exceeded.
Accessing the Notification Triggers app
The Notification Triggers section can be reached by using the bell icon on the left side menu or on the button on the homepage.
![]() |
Devices Overview
The Notification Triggers section opens with a devices overview, displaying a list of all devices in your EMS Site. Each device shows whether it supports this feature, and if so, how many enabled notification triggers it has compared to its total number of notification triggers.
Devices can be clicked to view and manage their notification triggers.
![]() |
Notification Triggers List
Users need the appropriate role and permissions to create, edit, disable, or delete notification triggers. |
After selecting a device, the triggers list displays all notification triggers configured for that device. Each trigger shows its name, current status, time and date of last activation and the number of conditions they consist of.
From this page you can:
Create new triggers using the Add notification trigger button
Enable/disable triggers using the toggle switch
Delete triggers using the delete option
View details by clicking on a trigger
![]() |
Notification Trigger Details
Clicking on a trigger opens the details page, which displays the trigger’s settings and configured conditions.
From this page you can:
- Edit the trigger using the Edit button, which opens the update form
- Manually reset the trigger using the Reset button (only visible when the trigger is in “awaiting reset” state)
![]() |
Create a Notification Trigger
When creating a trigger, you can only set the basic settings (name, message, notification level). To add activation and reset conditions, you need to edit the trigger after creation. |
To create a new notification trigger, click the Add notification trigger button from the triggers list. This opens the create form where you can configure the basic trigger settings.
![]() |
The following settings are configured when creating a notification trigger:
Name: A descriptive name for the trigger to easily identify its purpose.
Message: The notification message that will be displayed when the trigger activates.
Notification type: The type of notification that will be sent. This determines how the notification appears and can be filtered in the user’s notification settings. Available types are:
- Announcement - General informational notifications
- Success - Positive status notifications
- Warning - Cautionary notifications requiring attention
- Error - Critical notifications indicating problems
- Verified - Confirmation notifications
Edit a Notification Trigger
Changes to a trigger’s conditions may affect its current state. If you modify activation or reset conditions, the trigger may need to re-evaluate its state based on the new criteria. |
To edit an existing notification trigger, navigate to the trigger details page and click the Edit button. This opens the update form where you can modify the trigger settings and conditions.
![]() |
Notification trigger lifecycle
A notification trigger follows this lifecycle:
Awaiting Activation: The trigger starts in this state, or enters it after a reset, and monitors the activation conditions
Activation: When the required activation conditions are met, the trigger fires and sends a notification
Awaiting Reset: After activation, the trigger moves to this state and monitors the reset conditions
Reset: When the required reset conditions are met, the trigger returns to “Awaiting Activation” and can fire again. This could also be done manually via the Reset button on the trigger details page.
This two-phase approach prevents repeated notifications for the same ongoing condition. For example, if you set a trigger for when battery state of charge drops below 20%, the trigger will only send one notification when the condition is first met, then wait for the reset conditions (e.g., battery state of charge rises above 50%) before it can trigger again.
Activation and Reset Conditions
Notification triggers use a two-phase system with activation conditions and reset conditions to control when notifications are sent.
Each set of conditions require a validation strategy to be specified. It dictates how multiple conditions should be handled. The following strategies can be applied:
All conditions must be true: Every condition must be met simultaneously for the trigger to activate or reset
At least one condition must be true: The trigger activates or resets as soon as one of the conditions is met
Exactly one condition must be true: The trigger activates or resets when precisely one condition is met (not zero, not multiple)
Activation Conditions
Activation conditions determine when the trigger fires and sends a notification. You can configure one or more conditions that must be met for the trigger to activate.
![]() |
Reset Conditions
Reset conditions are essential to prevent notification spam. Without proper reset conditions, a trigger could potentially fire repeatedly for the same ongoing situation. |
Reset conditions determine when the trigger becomes ready to activate again after it has fired. Similar to activation conditions, you can configure one or more conditions.
![]() |
Condition Constraints
Constraints are the building blocks used to define both activation and reset conditions. The If and Between constraints can be used in either activation or reset conditions. The After constraint is only available for reset conditions.
When creating or editing a condition, the condition form opens where you can configure the constraint settings.
If
The If constraint allows you to create conditions based on device data values. You can monitor specific data series from your device and set thresholds using various operators.
![]() |
The following parameters are required for an If condition:
Data series: The device data value to monitor (e.g., solar power, grid power, battery state of charge).
Operator: The comparison operator to use:
- Equals to: Value matches exactly
- Above: Value is greater than the threshold
- Above or equals to: Value is greater than or equal to the threshold
- Under: Value is less than the threshold
- Under or equals to: Value is less than or equal to the threshold
- Not equals to: Value does not match
Value: The threshold value to compare against.
Between
If both begin time and end time are set to 00:00, all days are selected, and all months are selected, the constraint will be active continuously. |
The Between constraint allows you to specify time-based restrictions for when a condition should be evaluated. This is useful for creating triggers that only apply during certain hours, on specific days, or in specific months.
![]() |
The following parameters are available:
Start time: The start time for the condition window (24-hour format).
End time: The end time for the condition window (24-hour format).
Days: The days of the week when the condition should be active. Click on days to select or deselect them.
Months: The months of the year when the condition should be active. Click on months to select or deselect them. If all months are selected, the condition can be active year-round.
After
The After constraint adds a time delay requirement and is only available for reset conditions. This ensures a minimum time passes before the trigger can activate again.
![]() |
The following parameters are required:
Amount: The number of time units that must pass.
Time unit: The unit of time to use (minutes, hours, days, or weeks).
An example use case: After a low battery notification is triggered, you may want to wait at least 15 minutes before the trigger can fire again. Adding an After constraint with a 15-minute duration to the reset conditions ensures this delay.
Delete a Notification Trigger
Deleting a trigger is permanent and cannot be undone. If you want to temporarily stop a trigger from firing, consider disabling it instead. |
To permanently remove a notification trigger, use the delete option from the triggers list. You will be asked to confirm the deletion.
Manually Reset a Trigger
The Reset button is only visible when the trigger is currently in the “awaiting reset” state. |
If a trigger is in the “awaiting reset” state, you can manually reset it from the trigger details page by clicking the Reset button. This action immediately returns the trigger to the “awaiting activation” state, making it ready to fire again when activation conditions are met.
Enable/Disable Triggers
Triggers can be enabled or disabled from the triggers list without deleting them. A disabled trigger will not monitor conditions or send notifications, but its configuration is preserved.
To enable or disable a trigger, use the toggle switch next to the trigger in the list.
Combined views
Combined views can be reached by using the symbol on the left side menu or on the buttons on the homepage. Users can use this page to get an overview of all their EMS Site (Namespace) and the devices in a single table.
Users need the right role and read permissions for the information displayed in the combined view, otherwise it will not be shown. This can be enabled by enabling Combined views permission for the role of choice. |
![]() |
Devices
In the combined view for devices users can view details about devices in their joined EMS Site (Namespace). The user needs the role with correct permissions within the EMS Site to see the device in this overview, otherwise it won’t be displayed.
![]() |
The following details can be read from the devices:
- Online / offline status
- Name of the device
- EMS Site where the device is registered in
- Actual plant power
- Actual grid power
- Run status amount
- Amount of warnings
- Amount of errors
- Plant control status
- Status message
- Device software status
- Serial number of the device
- Product number of the device
- Date of last data call
- Date of last status call
Arrange and filter options
Users can arrange the columns of the table by dragging the top of the column to the left of right. It is also possible to select which columns should be displayed in the view, this can be done by opening the filter on the top right side of the columns.
![]() |
Device specific instructions
Some devices or brands require specific configuration steps or work-arounds to integrate with the Embion EMS Controller. This chapter lists these devices in alphabetical order by brand name.
ABL eM4 configuration
Consult the respective installation manual for detailed instructions on how to install the eM4 charger.
ABL eM4 Extender devices are currently not supported. ABL eM4 Extender devices are read via the Controller.
If all Extenders have been correctly added to the Controller, the total number of sockets (from the Controller and all Extenders combined) must be entered.
The software version of the eM4 Controller must be 2.2 or higher in order to be compatible with the Embion EMS Controller.
For single sockets ev chargers use only socket 1.
Aiswei configuration
The default ramp limit for reducing the inverter’s power is too low to guarantee good performance.
This setting can be adjusted in the Solplanet App:
Inverter configuration -> Active power settings -> Active power increase/decrease gradient
It is recommended to set this to the maximum value.
Amtron 4you RTU configuration
This chapter describes how to setup the Amtron 4you RTU EV charger models. Consult the respective installation manual for detailed instructions on how to install the Amtron charger.
Required settings on the Embion EMS Controller:
- RTU settings: 57600 baud, no parity, 2 stopbits, 8 databits
- Use device ID 50 (set by default at the Amtron RTU device)
Required settings on the Amtron 4you (300 series):
- On DIP switch Bank S1 set (at least) nr. 4 and 5 to ON position
Chint DTSU666 setup
There are two different versions of the Chint DTSU666 with CT clamps in circulation. Some versions already account for the CT ratio, while others do not.
The most common variant already takes the CT ratio into account and is available with the Chint DTSU666 protocol.
If during setup the current and power do not match the display (too low values), choose the DTSU666 (Gain) type.
EVBox
This chapter describe how to connect the RS485 cable to EVBox charging station models. Please consult the respective installation manual for detailed instructions on how to install the EVBox charger.
For information on how to install and / or commission the EVBox charger, please refer to the official documentation provided by EVBox. |
EVBox G3
To connect the G3, install an RS485 cable from the Embion EMS Controller to the RS485 port on the G3 HUB(s). The G3 Satellites should be connected to the G3 HUB following the instructions provided by EVBox.
![]() |
The RS485 cable should be connected to the RS485 port on each G3 HUB as shown in the figure below.
![]() |
EVBox G4
To connect the G4, install an RS485 cable from the Embion EMS Controller to the RS485 port on the G4 HUB(s). The G4 Satellites should be connected to the G4 HUB following the instructions provided by EVBox.
![]() |
The RS485 cable should be connected to the RS485 port on each G4 HUB as shown in the figure below.
![]() |
Flexicharge AC Charger Socket Settings
For the Flexicharge AC charger, socket 1 is available on port 502 and socket 2 on port 503. This port should not be changed, as it would disable support for socket 2.
If socket 2 is not available, please contact Flexicharge.
Solax X3 Ultra Hybrid - Firmware update
For the Solax X3 Ultra Hybrid there is a special firmware version. To update the inverter(s) to the correct firmware, please contact service.bnl@solaxpower.com